SPECIFICATIONS

Magic-Pak: HW/HWC

2-20

SRM-HW/HWC 2/99

5.

The

circulating air blower

shuts off approximately

90 seconds after

G

terminal on the

blower control

board

is de-energized (see note below).

FAN ON

Low Voltage

1.

When the switch on the

thermostat

is moved to the

“FAN ON” position, a 24-volt signal is sent to

G

.

2.

With

G

energized, the

blower control board

starts

a countdown to fan “on”. After approximately 15
seconds, the fan starts (see note below).

3.

The

blower control board

closes a relay on the

board, sending line voltage to the terminal marked

COOL

on the board. This starts the

circulating air

blower

.

4.

When the switch at the

thermostat

is moved to the

“OFF” position, the 24-volt signal to the

blower

control board

is interrupted. With no signal at the

G

terminal, the

blower control board

starts a

countdown to fan “off”. Approximately 90 seconds
later, a relay on the

blower control board

opens

(see note below). This interrupts the power to and
stops the

circulating air blower

.

Note:

Heatcraft

blower control boards have a

G

“on”

delay of 15 seconds and an “off” delay of 90
seconds.

Tridelta

blower control boards have no

“on” time delay and a 60 -130 second “off” delay.

Advertising