Service reference manual unit components, Main (high) limit switch (*52) – Armstrong World Industries HWC PREMIER 183 User Manual

Page 82

Advertising
background image

Service Reference Manual

UNIT COMPONENTS

5-19

SRM-HW/HWC 2/99

Main (High) Limit Switch (*52)

A Normally Closed control that opens if abnormally high circulating air
temperatures occur. It is an automatic reset control.

Note: Several different main limit switches are used.

Refer to the parts

list for the correct limit switch.

N.O. (Normally Open)

Terminal

N.C. (Normally Closed)

Terminal

Common Terminal

7

"

FIGURE 5-15 Camstat Main Limit Switch

Camstat Model L59-7B-220-30
Armstrong P/N: 01150A008
Setting: 220°F

FIGURE 5-16 Main Limit Switch

3.05

(+/ .05

)

"

– "

Manufacturer P/N: INT17L-2107
Armstrong P/N: 40154B007
Open Setting: 190°F
Closed Setting: 160°F

Advertising