Service reference manual unit components, Heatcraft model ibc-h4c401 – Armstrong World Industries HWC PREMIER 183 User Manual

Page 70

Advertising
background image

Service Reference Manual

UNIT COMPONENTS

5-7

SRM-HW/HWC 2/99

Heatcraft Model IBC-H4C401

Blower Control Board Specifications

Manufacturer: United Technologies
Model: 1010-611
Armstrong P/N 39029B002
Operating Voltage: 18-30VAC 60 Hz
60 Hz Power Requirement: 4 VA max.
Operating Temperature: – 40°F to +170°F
Wiring Connections: All Male .250" x .032" Quick Connect Tabs

Performance Specifications (all timings +/– 1 second):

Heating: On Delay Timing - 60 seconds

Off Delay Timing - 90 seconds

Cooling: On Delay Timing - 15 seconds

Off Delay Timing - 90 seconds

Heating and Cooling Output Rating:

12 F.L.A., 30 L.R.A. at 120VAC for 100,000 Cycles
10 F.L.A., 30 L.R.A. at 240VAC for 100,000 Cycles

Both heat and cool outputs cannot be energized simultaneously.

HEATCRAFT

M2

COOL

HEAT

W

C

R

G

L1

M1

39029B

002

L1 Line Voltage

Heat Speed

L1 Power Out

Cool Speed

L1 Power Out

Dumb Terminal
(Park)

Dumb Terminal

(Park)

24 VAC Heat Call

24 VAC Common

24 VAC Power

24 VAC (Fan On/Cooling Fan Auto)

FIGURE 5-5

Heatcraft Blower Control Board IBC-H4C401