Troubleshooting magic-pak: hw/hwc – Armstrong World Industries HWC PREMIER 183 User Manual

Page 195

Advertising
background image

9-10

TROUBLESHOOTING

Magic-Pak: HW/HWC

SRM-HW/HWC 8/99

Performance Tests (Chassis Installed in Unit) - cont.

Total

Air Vol.

(CFM)

Enter.

DB/WB

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Outdoor Air Temperature Entering Outdoor Coil

85°

95°

105°

115°

775
850
925
775

850
925
775
850
925

75°/63°

80°/67°

85°/71°

76

46

100

77

46

110

78

46

120

79

47

129

78

51

100

79

47

110

80

48

120

81

48

129

80

57

100

81

49

111

82

49

120

83

50

130

82

60

102

84

51

111

85

51

121

87

52

131

84

65

102

85

56

112

87

52

121

88

53

131

85

70

102

87

60

112

88

54

121

89

53

131

89

72

103

90

63

112

92

55

122

93

55

132

91

77

104

92

69

113

94

61

123

95

57

133

93

82

104

94

72

113

96

64

123

97

58

133

Based on a normally installed cooling chassis

TABLE 9-4

HWC302 Performance Test (Chassis Installed)

Total

Air Vol.

(CFM)

Enter.

DB/WB

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Suction

Pressure

Suction

Temp.

Liquid
Temp.

Outdoor Air Temperature Entering Outdoor Coil

85°

95°

105°

115°

700
800
900
700
800
900

700
800
900

75°/63°

80°/67°

85°/71°

77

47

98

78

46

108

79

47

117

80

48

128

79

52

98

80

47

108

81

48

117

82

49

128

81

57

99

82

50

109

83

49

118

84

50

128

82

60

99

83

51

109

85

50

118

86

51

128

84

65

100

85

56

109

87

52

119

88

52

129

86

70

100

87

60

110

89

55

119

90

53

129

87

71

100

88

61

110

89

53

119

90

54

129

89

76

101

90

68

110

91

59

120

92

55

130

91

81

101

92

71

110

93

62

120

94

56

130

Based on a normally installed cooling chassis

TABLE 9-3

HWC242 Performance Test (Chassis Installed)

Advertising