4.7. Control Terminal Wiring

All analog signal cables should be suitably shielded. Twisted pair cables are recommended.

Power and Control Signal cables should be routed separately where possible, and must not be routed parallel to each other

Signal levels of different voltages e.g. 24 Volt DC and 110 Volt AC, should not be routed in the same cable.

Maximum control terminal tightening torque is 0.5Nm

4.8. Connection Diagram

4.8.1. Power Terminal Designations

Incoming Mains Power Supply
For 1 Phase Supply, connect to
L1/L and L2/N terminals.
For 3 Phase Supply, connect to
L1, L2 & L3 terminals.
Phase sequence is not
important.

Motor Connections
Connect the motor to the U, V & W
terminals.
The motor earth must be connected
to the drive
Optional Brake Resistor & DC Bus
Connections
Where a Brake resistor is used, it
must be connected to the BR+ and
DC- terminals

Protective Earth / Ground
connection.
The drive must be Earthed /
Grounded

4.8.2. Control Terminal Connections & Factory Settings

Open

Closed

+24V Supply (100mA) / External Input

+24V

1

Digital Input 1

Run (Enable)

Stop

DIN1

2

Digital Input 2

Forward Rotation

Reverse Rotation

DIN2

3

Digital Input 3

Analog Speed Ref

Preset Speed

DIN3

4

Digital Inputs : 8 – 30 Volt DC
+ 10 Volt, 10mA Output

+10V

5

Analog Input 1

AIN1

6

0V

7

0V

Output Speed

Analog Output : 0 – 10 Volt / 4-20mA, 20mA Max

8

AOUT1

0 Volt Supply / External Input

0V

9

0V

Output Current

Analog Input 2

AIN2

10

Analog Output : 0 – 10 Volt / 4-20mA, 20mA Max

11

AOUT2

External Hardware Enable Circuit

STO+

12

STO-

13

Relay Contacts
250VAC / 30VDC
5A Maximum

14

RL1-C

Healthy
/ Fault

15

RL1-NO

16

RL1-NC

17

RL2-A

Running

18

RL2-B