Beijer Electronics BFI-H2 V1.12 User Manual

Page 61

Advertising
background image

User Guide Revision 1.12

61

P0-29

Drive Type

-

-

-

-

Displays the type details of the drive: Three entry display:
First display = Frame size and input voltage level
Second display = Power rating
Third display = Output Phase Count

P0-30

Serial Number

-

-

-

-

Displays the unique serial number of the drive. Dual entry display:
First display = Serial number (MSB), Second display = Serial number (LMSB)

P0-31

Run Time Since Date of Manufacturer

0

-

-

HH:MM:SS

Two entry display: First display shows hours. Second display shows minutes and seconds
Displays the total operating time of the drive.

P0-32

Run Time Since Last Trip 1

0

99999H

-

HH:MM:SS

Two entry display: First display shows hours. Second display shows minutes and seconds
Displays the total operating time of the drive since the last fault occurred. Run-time clock stopped by drive disable (or trip), reset on
next enable only if a trip occurred. Reset also on next enable after a drive power down.

P0-33

Run Time Since Last Trip 2

0

99999H

-

HH:MM:SS

Two entry display: First display shows hours. Second display shows minutes and seconds
Displays the total operating time of the drive since the last fault occurred. Run-time clock stopped by drive disable (or trip), reset on
next enable only if a trip occurred (under-volts not considered a trip) – not reset by power down / power up cycling unless a trip
occurred prior to power down.

P0-34

Run Time Since Last Disable

0

99999H

-

HH:MM:SS

Two entry display: First display shows hours. Second display shows minutes and seconds
Displays the total operating time of the drive since the last Run command was received.

P0-35

Fan Run Time

0

99999H

-

HH:MM:SS

Displays the total operating time of the drive internal cooling fans.
Two entry display: First display shows user resettable time (reset with P6-22). Second display shows none resettable time.
This is used for scheduled maintenance information

P0-36

DC Bus Voltage Log (256ms)

-

-

-

-

Diagnostic log for DC bus voltage. Values logged every 256mS with 8 samples total. Logging suspended on drive trip.

P0-37

DC Bus Voltage Ripple Log (20ms)

-

-

-

-

Diagnostic log for DC bus voltage ripple. Values logged every 20mS with 8 samples total. Logging suspended on drive trip.

P0-38

Heatsink Temperature Log (30s)

-

-

-

-

Diagnostic log for heatsink temperature. Values logged every 30S with 8 samples total. Logging suspended on drive trip.

P0-39

Ambient Temperature Log (30s)

-

-

-

-

Diagnostic log for drive ambient temperature. Values logged every 30S with 8 samples total. Logging suspended on drive trip.

P0-40

Motor Current Log (256ms)

-

-

-

-

Diagnostic log for Motor Current. Values logged every 256mS with 8 samples total. Logging suspended on drive trip.

Note:

The above parameters (P0-36 to P0-40) are used to store the history of various measured levels within the drive at various regular
time intervals prior to a trip. The values are frozen when a fault occurs and can be used for diagnostic purposes.

P0-41

Over Current Fault Counter

0

-

0

-

P0-42

Over Voltage Fault Counter

0

-

0

-

P0-43

Under Voltage Fault Counter

0

-

0

-

P0-44

Heatsink Over Temperature Fault Counter

0

-

0

-

P0-45

Brake Chopper Short Circuit Fault Counter

0

-

0

-

P0-46

Ambient Over Temperature Fault Counter

0

-

0

-

Note

These parameters (P0-41 to P0-46) contain a record of how many times certain critical faults have occurred during a drives operating
lifetime. This provides useful diagnostic data

P0-47

I/O comms fault counter

0

-

0

-

Displays the number of communication errors detected by the I/O processor in messages received from the power stage processor
since the last power up

P0-48

DSP comms fault counter

0

-

0

-

Displays the number of communication errors detected by the Power Stage processor in messages received from the I/O processor
since the last power up

P0-49

Modbus RTU / BACnet Fault Counter

0

-

0

-

This parameter is incremented every time an error occurs on the Modbus RTU communication link. This information can be used for
diagnostic purposes.

P0-51

Last Fire Mode Activation Time

-

-

-

Hours

Parameter contains a start time for the last Fire Mode event (see section 7.8 – Fire Mode Function). Value recorded in P0-51 is taken
from Drive Lifetime Operating Time parameter (P0-31)

P0-52

Fire Mode Activation Period

-

-

-

Hours

Parameter contains a record of the number of minutes that the drive has been run in Fire Mode (see section 7.8 – Fire Mode
Function).

P0-53

Current Phase U offset and Reference

-

-

-

-

Internal Value, Contact your local Drive Distributor

P0-54

Current Phase V offset and Reference

-

-

-

-

Internal Value, Contact your local Drive Distributor