10. Digital Input Functions

10.1. Digital Input Configuration Parameter P1-13

P1-13

*(2)

Local (Hand)

Control Function

Digital Input 1

(Terminal 2)

Digital Input 2

(Terminal 3)

Digital Input 3

(Terminal 4)

Analog Input 1

(Terminal 6)

Analog Input 2

(Terminal 10)

Notes

0

N/A

All functions User defined in Menu 9 or configured through PLC function in OptiTools studio software
suite.

1

*(3)



Analog Input 2

O: Stop
C: Run / Enable

O: Normal Operation
C: Preset 1 / PI Set-point
2

O: Remote Ctrl
C: Local Ctrl

Analog In 1

Analog In 2

When Input 3 is Closed:
Speed Reference =
Analog Input 2
Start Command = Input 1

In PI Mode, Analog Input
1 must be used for
feedback

2

O: No Function
C: Momentary Start

O: Stop (Disable)
C: Run Permit

O: Remote Ctrl
C: Local Ctrl

Analog In 1

Analog In 2

3

O: Stop
C: Run / Enable

O: Forward
C: Reverse

O: Remote Ctrl
C: Local Ctrl

Analog In 1

Analog In 2

4

O: Stop
C: Run / Enable

O: Fire Mode

*(1)

C: Normal Operation

* (1)

O: Remote Ctrl
C: Local Ctrl

Analog In 1

Analog In 2

5



Preset Speeds

O: Stop
C: Run / Enable

O: Preset Speed 1
C: Preset Speed 2

O: Remote Ctrl
C: Local Ctrl

Analog In 1

O: Ext Trip
C: Normal Operation

When Input 3 is Closed:
Speed Reference =
Preset Speed 1 / 2
Start Command = Input 1

6

O: No Function
C: Momentary Start

O: Stop (Disable)
C: Run Permit

O: Remote Ctrl
C: Local Ctrl

Analog In 1

O: Preset 1
C:Preset 2l

7

O: Stop
C: Run / Enable

O: Forward
C: Reverse

O: Remote Ctrl
C: Local Ctrl

Analog In 1

O: Preset 1
C:Preset 2

8

O: Stop
C: Run / Enable

O: Fire Mode

*(1)

C: Normal Operation

* (1)

O: Remote Ctrl
C: Local Ctrl

Analog In 1

O: Preset 1
C:Preset 2

9

*(3)




Keypad Speed

Reference

O: Stop
C: Run / Enable

O: Normal Operation
C: Preset 1 / PI Set-point
2

O: Remote Ctrl
C: Local Ctrl

Analog In 1

Analog In 2

When Input 3 is Closed:
Speed Reference =
Keypad
Start Command =
Determined by P2-37

10

*(3)

O: Stop
C: Run / Enable

O: Normal Operation
C: Preset 1 / PI Set-point
2

O: Remote Ctrl
C: Local Ctrl

Analog In 1

O: Ext Trip
C: Normal Operation

11

O: No Function
C: Momentary Start

O: Stop (Disable)
C: Run Permit

O: Remote Ctrl
C: Local Ctrl

Analog In 1

Analog In 2

12

O: Stop
C: Run Fwd

O: Forward
C: Reverse

O: Remote Ctrl
C: Local Ctrl

Analog In 1

Analog In 2

13

O: Stop
C: Run Fwd

O: Fire Mode

*(1)

C: Normal Operation

* (1)

O: Remote Ctrl
C: Local Ctrl

Analog In 1

Analog In 2

Notes
*(1): Logic shown is as per the default setting. Fire mode logic can be configured through parameter P8-09.
*(2): Default setting for P1-13 = 1
*(3): When the drive is in PID control (P1-12 = 3) and digital preset reference is selected (P3-05 = 0) then P1-13 can be set to 1, 9, or 10 to allow

selection between two independent digital references using digital input 2. Digital preset reference 1 and 2 are set in P3-06 and P3-15
respectively.


Note: “Motor thermistor trip” connection is via analog input 2 and is configured by parameter P2-33 (



). The “External trip” input is no

longer utilised for the thermistor input (this is different to the ODP drive and E2 drive).