Beijer Electronics BFI-H2 V1.12 User Manual

Page 51

Advertising
background image

User Guide Revision 1.12

51



P2-12

Analog Output 1 Format (Terminal 8)

-

-



-



= 0 to10V,



= 10 to 0V,



= 0 to 20mA



= 20to 0mA



= 4 to 20mA



= 20 to 4mA

P2-13

Analog Output 2 Function (Terminal 11)

0

11

9

-

Digital Output Mode. Logic 1 = +24V DC

0 : Drive Enabled (Running). Logic 1 when the drive is enabled (Running)
1 : Drive Healthy. Logic 1 When no Fault condition exists on the drive
2 : At Target Frequency (Speed). Logic 1 when the output frequency matches the set-point frequency
3 : Output Frequency > 0.0. Logic 1 when the motor runs above zero speed
4 : Output Frequency >= Limit. Logic 1 when the motor speed exceeds the adjustable limit
5 : Output Current >= Limit. Logic 1 when the motor current exceeds the adjustable limit
6 : Reserved. No Function
7 : Analog Input 2 Signal Level >= Limit. Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit

Analog Output Mode (Format set in P2-14)

8 : Output Frequency (Motor Speed). 0 to P-01
9 : Output (Motor) Current. 0 to 200% of P1-08
10 : Reserved. No Function
11 : Output (Motor) Power. 0 to 150% of drive rated power

Note:

When using settings 4 – 7, parameters P2-19 and P2-20 are used to control the output behaviour. The output will switch to Logic 1
when the selected signal exceeds the value programmed in P2-19, and return to Logic 0 when the signal falls below the value
programmed in P2-20.

P2-14

Analog Output 2 Format (Terminal 11)

-

-



-



= 0 to10V.



= 10 to 0V,



= 0 to 20mA



= 20to 0mA



= 4 to 20mA



= 20 to 4mA

P2-15

Relay Output 1 Function (Terminals 14, 15 & 16)

0

7

1

-

Selects the function assigned to Relay Output 1. The relay has normally open and normally closed contacts. Logic 1 indicates the relay
is active, and therefore the normally open contact is closed (terminals 14 and 15 will be linked together) and the normally closed
contact is opened (terminals 14 and 16 will no longer be connected together).
0 : Drive Enabled (Running). Logic 1 when the motor is enabled
1 : Drive Healthy. Logic 1 when power is applied to the drive and no fault exists
2 : At Target Frequency (Speed). Logic 1 when the output frequency matches the set-point frequency
3 : Output Frequency > 0.0 Hz. Logic 1 when the drive output frequency to the motor is exceeds 0.0Hz
4 : Output Frequency >= Limit. Logic 1 when the motor speed exceeds the adjustable limit
5 : Output Current >= Limit. Logic 1 when the motor current exceeds the adjustable limit
6 : Reserved. No Function
7 : Analog Input 2 Signal Level >= Limit. Logic 1 when the signal applied to the Analog Input 2 exceeds the adjustable limit
8 : Reserved. No Function
9 : Fire Mode Active. Logic 1 when the drive in running in Fire Mode (Fire Mode input is active).
10 : Maintenance Due. Logic 1 when Maintenance Timer expires indicating that Maintenance is now due.
11 : Drive Available. Logic 1 when drive is in Auto-mode, no trips are present, and the safety circuit is enabled indicating that drive is
ready for automatic control.

Note:

When using settings 4 – 7, parameters P2-16 and P2-17 are used to control the output behaviour. The output will switch to Logic 1
when the selected signal exceeds the value programmed in P2-16, and return to Logic 0 when the signal falls below the value
programmed in P2-17.

P2-16

Adjustable Threshold 1 Upper Limit (AO1 / RO1)

P2-17

200

100.0

%

Setting the upper limited value for P2-11 and P2-15, please refer to P2-11 or P2-15

P2-17

Adjustable Threshold 1 Lower Limit (AO1 / RO1)

0

P2-16

0.0

%

Setting the lower limited value for P2-11 and P2-15, please refer to P2-11 or P2-15.