Parameter group 7 – reserved (not available) – Beijer Electronics BFI-H2 V1.12 User Manual

Page 57

Advertising
background image

User Guide Revision 1.12

57

P6-10

PLC Function Enable

0

1

0

-

This parameter enables the PLC function support and must be set to 1 before any PLC program loaded into the drive will operate.
When set to 0, the PLC program will be disabled.
0: Disabled
1: Enabled

P6-11

Speed Hold Time On Enable

0

250

0

Seconds

Defines a time period for which the drive will run at Preset Speed 7 (P2-07) when the Enable signal is applied to the drive. This feature
can be used on pumps to provide a reverse spin on start up, to clear potential blockages.

P6-12

Speed Hold Time On Disable

0

250

0

Seconds

Defines a time period for which the drive will run at Preset Speed 8 (P2-08) following removal of the Enable signal, before ramping to
stop. This feature can be used in applications such as underground PCP pumps to provide an unwind of the driveshaft on stopping

P6-18

DC Injection Braking Voltage

0

25

0

%

Sets the level of DC voltage as a percentage of the nominal voltage (P1-07) that is applied to the motor when a stop command is
received.

P6-22

Reset Cooling Fan Timer

0

1

0

-

Setting to 1 resets internal Fan run-time counter to zero (as displayed in P0-35).

P6-23

Reset kWh Meter

0

1

0

-

Setting to 1 resets internal kWh meter to zero (as displayed in P0-26 and P0-27)

P6-24

Service Time Interval

0

60000

5000

Hours

Defines the service interval counter period. This defines the total number of run time hours which must elapse before the service
indicator is shown on the drive OLED display.
When P6-25 is set to 1, the internal service interval counter is set to this value.

P6-25

Reset Service Indicator

0

1

0

-

When this parameter is set to 1, the internal service interval counter is set to the value defined in P6-24

P6-26

Analog Output 1 Scaling

0

500

100

%

Defines the scaling factor as a percentage used for Analog Output 1

P6-27

Analog Output 1 Offset

-500

500

0

%

Defines the offset as a percentage used for Analog Output 1

P6-28

P0-80 Display Index

0

127

0

-

This parameter defines the index of the internal variable, the value of which will be displayed in P0-80.
This is usually used in conjunction with the PLC function.

P6-29

Save User Parameters as Default

0

1

0

-

Setting this parameter to 1 saves the current parameter settings as "User default parameters". When the User carries out a 3-button
default parameter command (UP, DOWN and STOP), the parameter saved when P6-29 was last set to 1 will be restored.

P6-30

Level 3 Access Code Definition

1

9999

201

-

Defines the access code which must be entered into P1-14 to allow access to the Advanced Parameters in Groups 6 to 9 (Menu 8
accessible through level 2 security).


11.6. Parameter Group 7 – Reserved (not available)

Menu group 7 parameters are not used by the HVAC drive and serve no function in drive set-up / configuration.

11.7. Parameter Group 8 – HVAC Function Specific Parameters

Par

Parameter Name

Minimum

Maximum

Default

Units

P8-01

Stir Interval Duration

0

60000

0

mins

Period of inactivity (drive is standby mode) that will trigger the drive stir function.

P8-02

Stir Activation Time

1

6000

10

Secs

Set the time period that the stir function will be active once triggered (excludes time for deceleration to stop)

Note:

For full detail of Stir function configuration see section 7.6, Pump Stir Function, or contact your local drive distributor

P8-03

Cleaning Function Select

0

3

0

-

This parameter configures the drive conditions that will cause activation of the automatic pump clean function.
0 = Disabled
1 = Active on Start up Only.
The pump cleaning function operates every time the pump is started.
2 = Active on start up and over-torque detection. The pump cleaning function operates every time the pump is started, and also in
the event that the drive detects a possible pump blockage during normal operation. This requires the Load Profile Monitoring
function to be active and commissioned for correct operation, see parameter P8-06.
3 = Active on over-torque detection only. The pump cleaning function operates only when a possible pump blockage is detected
during normal operation. This requires the Load Profile Monitoring function to be active and commissioned for correct operation, see
parameter P8-06.
Note: The pump clean function can also be activated by digital input configured in group 9 parameters.

P8-04

Cleaning Time

0

600

0

Secs

Sets the time period for the operation of the pump cleaning cycle. When bi-directional pump cleaning is selected, the time interval is
used twice, once in each direction.