Beijer Electronics BFI-H2 V1.12 User Manual

Page 59

Advertising
background image

User Guide Revision 1.12

59

P8-17

Assist Pump Start Speed

P8-18

P1-01

0

Hz / RPM

H2 drive upper speed Staging threshold. When the drive output increases beyond this threshold the next Staging pump is switch on.
The Pump staging settle time must then expire before additional staging pumps can be brought on or off line. Priority for Staging
pump switch on is always given to the pump with lowest run time accumulated.

P8-18

Assist Pump Stop Speed

0

P8-17

0

Hz / RPM

H2 drive lower speed Staging threshold. When the drive output decreases below this threshold one of the Staging pumps currently
operating is switch off. The Pump staging settle time must then expire before additional staging pumps can be brought on or off line.
Priority for Staging pump switch off is always given to the pump with highest run time accumulated.

P8-19

Pump Settling Time

10

600

10

Secs

Parameter sets a time delay for pump staging whereby, following switch in or switch out of a staging pump, further pumps are not
permitted to be switched in or out until this time period has elapsed. This parameter should be set to allow adequate settle time
between staging pump transitions.

P8-20

Pump Master Clock Reset

0

1

0

-

Master drive in pump staging monitors and maintains duty run times for all available staging pumps. All clocks are available to view in
P0-20. P8-20 provides the master reset to all run time clocks used for Pump Staging Function (all clocks set to 0).

Note:

For full detail of Pump Staging function configuration see section 7.1 and 7.2, or contact your local drive distributor



-

11.8. Parameter Group 9 – Advance drive control logic configuration

Menu group 9 parameters are detailed in the following Reference Table. They can be accessed through the drive keypad by setting advanced
security level access (P1-14 = 201) or through the OptiTools Studio software suite. Care should be taken in adjusting these parameters. Please
contact your local distributor for further assistance.

P9-01

Enable Input Source

Defines the source of the signal to be used for the Enable input

P9-02

Fast Stop Input Source

Defines the source of the signal to be used for the Fast Stop input

P9-03

Forward Run Input Source

Defines the source of the signal to be used for the Forward Run input

P9-04

Reverse Run Input Source

Defines the source of the signal to be used for the Reverse Run input

P9-05

Latch Function Enable

Latch function enable control for the run signals (P9-03 and P9-04)

P9-06

Reverse Enable Source

Defines the source of the signal to be used for Reverse run direction control

P9-07

Reset Input Source

Defines the source of the signal to be used for the Reset input

P9-08

External Trip Input Source

Defines the source of the signal to be used for the External trip input

P9-09

Terminal Control Override Source

Defines the source of the signal to be used for the terminal control override

P9-10

Speed Source 1

Defines the Reference Value used for Speed Source 1

P9-11

Speed Source 2

Defines the Reference Value used for Speed Source 2

P9-12

Speed Source 3

Defines the Reference Value used for Speed Source 3

P9-13

Speed Source 4

Defines the Reference Value used for Speed Source 4

P9-14

Speed Source 5

Defines the Reference Value used for Speed Source 5

P9-15

Speed Source 6

Defines the Reference Value used for Speed Source 6

P9-16

Speed Source 7

Defines the Reference Value used for Speed Source 7

P9-17

Speed Source 8

Defines the Reference Value used for Speed Source 8

P9-18

Speed Select Input 0

Speed multiplex input 0

P9-19

Speed Select Input 1

Speed multiplex input 1

P9-20

Speed Select Input 2

Speed multiplex input 2

P9-21

Preset Speed Select Input 0

Preset speed selection multiplex input 0

P9-22

Preset Speed Select Input 1

Preset speed selection multiplex input 1

P9-23

Preset Speed Select Input 2

Preset speed selection multiplex input 2

P9-28

Remote Up Button Input Source

Defines the source of the signal to be used as the Remote UP button

P9-29

Remote Down Button Input Source

Defines the source of the signal to be used as the Remote DOWN button

P9-32

Fire mode trigger input selection

Defines the source of the signal to be used for the Fire mode input

P9-33

Analog Output 1 Control Source

This parameter specifies the relay output 1 control source

P9-34

Analog Output 2 Control Source

This parameter specifies the relay output 2 control source

P9-35

Relay 1 Control Source

This parameter specifies the relay output 1 control source

P9-36

Relay 2 Control Source

This parameter specifies the relay output 2 control source

P9-37

Scaling Source Control

This parameter specifies the scaling control source

P9-38

PID Reference Source Control

This parameter specifies the PID reference source

P9-39

PID Feedback Source Control

This parameter specifies the PID feedback source

P9-41

Relay outputs 3, 4, 5 Function Select

Defines the function of Extended I/O relay outputs 3, 4 and 5

P9-42

Clean Trigger Input (Edge)

Defines the source of the signal to be used for the pump clean enable input

P9-43

Bypass Trigger Input

Defines the source of the signal to be used for the Bypass function enable input

P9-44

PID 2nd Digital Reference Select Input

Defines the source of the signal to be used for selecting the 2nd digital reference for PID


Advertising