12. Serial communications

12.1. RS-485 communications

The drive has an RJ45 connector located within the wiring enclosure of the drive. This connector allows the user to set up a drive network via a
wired connection. The connector contains two independent RS485 connections, one for manufacturer proprietary Protocol and one for
Modbus RTU / BACnet. Both connections can be used simultaneously.

The electrical signal arrangement of the RJ45 connector is shown as follows:

Not Used
Not Used
0 Volt
Optibus / Remote Keypad / PC Connection -
Optibus / Remote Keypad / PC Connection +
+24 Volt Remote Keypad Power Supply
RS 485- Modbus RTU / BACnet
RS 485+ Modbus RTU / BACnet

Warning:

This is not an Ethernet connection.
Do not connect directly to an
Ethernet port.


The Optibus data link is used for the Master / Slave function (refer to the Advanced User Guide for further information). Up to 62 slaves can be
connected to one master drive.

The Modbus interface allows connection to a Modbus RTU network as described below.

12.2. Modbus RTU Communications

12.2.1. Modbus Telegram Structure

The drive supports Master / Slave Modbus RTU communications, using the 03 Read Holding Registers and 06 Write Single Holding Register
commands. Many Master devices treat the first Register address as Register 0; therefore it may be necessary to convert the Register Numbers
detail in section 12.2 by subtracting 1 to obtain the correct Register address. The telegram structure is as follows:-

Command 03 – Read Holding Registers

Master Telegram

Length

Slave Response

Length

Slave Address

1

Byte

Slave Address

1

Byte

Function Code (03)

1

Byte

Starting Address

1

Byte

1

st

Register Address

2

Bytes

1

st

Register Value

2

Bytes

No. Of Registers

2

Bytes

2

nd

Register Value

2

Bytes

CRC Checksum

2

Bytes

Etc...

CRC Checksum

2

Bytes

Command 06 – Write Single Holding Register

Master Telegram

Length

Slave Response

Length

Slave Address

1

Byte

Slave Address

1

Byte

Function Code (06)

1

Byte

Function Code (06)

1

Byte

Register Address

2

Bytes

Register Address

2

Bytes

Value

2

Bytes

Register Value

2

Bytes

CRC Checksum

2

Bytes

CRC Checksum

2

Bytes