Ip20 quick start up guide – Beijer Electronics BFI-H2 V1.12 User Manual

Page 4

Advertising
background image

User Guide Revision 1.12


4

IP20 Quick Start Up Guide



AC Supply Connection

Supply Voltage

3 Phase Units : Connect L1 L2 L3, PE

200 – 240 Volts + / - 10%

1 Phase Units : Connect L1, L2, PE

380 – 380 Volts + / - 10%

Fuses or MCB

o

Check the Drive Rating Information in section 13.4


Help Card

Display Information can be found in section 5.1


Keypad Operation can be found in section 5.1


IMPORTANT!

Hardware Enable









Link the terminals as shown, optionally through switch contacts to enable
drive operation


Control Terminals
Based on the factory default parameter settings

Run – Stop

10K Speed Pot

Close the switch to run (enable), open to stop

Motor Cable

o

For correct cable size in section 13.4

o

Observe the maximum permissible motor cable length

o

For Motor cable lengths > 50 metres, an output filter is
recommended

o

Use a screened (shielded cable)


Motor Connection

o

Check for Star or Delta connection according to the motor
voltage rating in section 4.5.

o

Motor Nameplate Details

o

Motor Rated Voltage : P1-07

o

Motor Rated Current : P1-08

o

Motor Rated Frequency : P1-09

o

Motor Rated Speed (Optional) : P1-10