Warning – Bryant 2-stage Deluxe Induced-Combustion 4-way Multipurpose 120 User Manual

Page 15

Advertising
background image

15

30-IN. MIN

WORK AREA

6″ MIN*

TYPE-B

VENT

17

3

/

4

22″

SHEET

METAL

SEDIMENT

TRAP

EQUIPMENT MANUAL

SHUT-OFF GAS VALVE

LINE CONTACT ONLY PERMISSIBLE BETWEEN

LINES FORMED BY INTERSECTIONS OF

THE TOP AND TWO SIDES OF THE FURNACE

JACKET AND BUILDING JOISTS,

STUDS, OR FRAMING.

GAS

ENTRY

17

3

/

4

″ OVER ALL

4

3

/

4

″ UNDER DOOR

1″ UNDER FURNACE

EXTEND OUT 12″ OUT

FROM FACE OF DOOR

* WHEN USED WITH

SINGLE WALL VENT

CONNECTIONS

UNION

A03177

Fig. 17 -- Typical Attic Installation

Not all horizontal furnaces are approved for side return air
connections. (See Fig. 20.)
FILTER ARRANGEMENT

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal

injury, or death.
Never operate a furnace without a filter or with filter access

door removed.

!

WARNING

There are no provisions for an internal filter rack in these

furnaces. An external filter rack is required.
This furnace is shipped with a factory--supplied Media Filter

Cabinet. The Media Filter Cabinet uses either a factory--supplied
standard 1--inch filter or 4--inch wide Media Filter which can be

purchased separately.
Refer to the instructions supplied with Media Cabinet for

assembly and installation options.
AIR DUCTS
General Requirements
The duct system should be designed and sized according to

accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and

Air Conditioning Contractors National Association (SMACNA)

or American Society of Heating, Refrigerating and Air
Conditioning Engineers (ASHRAE) or consult The Air Systems

Design Guidelines reference tables available from your local
distributor. The duct system should be sized to handle the

required system design CFM at the design external static pressure.

The furnace airflow rates are provided in Table 5--Air Delivery
CFM (With Filter).
When a furnace is installed so that the supply ducts carry air
circulated by the furnace to areas outside the space containing the

furnace, the return air shall also be handled by duct(s) sealed to

the furnace casing and terminating outside the space containing
the furnace.

Secure ductwork with proper fasteners for type of ductwork used.
Seal supply-- and return--duct connections to furnace with code

approved tape or duct sealer.
NOTE: Flexible connections should be used between ductwork
and furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be

insulated to enhance system performance. When air conditioning
is used, a vapor barrier is recommended.
Maintain a 1--in. clearance from combustible materials to supply

air ductwork for a distance of 36 in. horizontally from the
furnace. See NFPA 90B or local code for further requirements.
Ductwork Acoustical Treatment
NOTE
: Metal duct systems that do not have a 90_ elbow and 10
ft of main duct to the first branch take--off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used
if constructed and installed in accordance with the latest edition of
SMACNA construction standard on fibrous glass ducts. Both
acoustical lining and fibrous ductwork shall comply with NFPA
90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct
shall be provided with a removable access panel. This opening

shall be accessible when the furnace is installed and shall be of
such a size that the heat exchanger can be viewed for possible

openings using light assistance or a probe can be inserted for

sampling the air stream. The cover attachment shall prevent leaks.
Upflow and Horizontal Furnaces
Connect supply--air duct to flanges on furnace supply--air outlet.
Bend flange upward to 90_ with wide duct pliers. (See Fig. 14.)

The supply--air duct must be connected to ONLY the furnace
supply--outlet--air duct flanges or air conditioning coil casing

(when used). DO NOT cut main furnace casing side to attach

supply air duct, humidifier, or other accessories. All accessories
MUST be connected to duct external to furnace main casing.

312A

Advertising