Warning, Caution – Bryant 2-stage Deluxe Induced-Combustion 4-way Multipurpose 120 User Manual

Page 35

Advertising
background image

35

In Canada: Per section 8.24.2 of the CAN/CSA--B149.1--05,
any listed mechanical venter may be used, when approved by the

authority having jurisdiction.
Select the listed mechanical venter to match the Btuh input of the

furnace being vented. Follow all manufacturer s installation

requirements for venting and termination included with the listed
mechanical venter.

START--UP, ADJUSTMENT, AND SAFETY

CHECK

Step 1 — General

FIRE HAZARD
Failure to follow this warning could result in personal

injury, death and/or property damage.
This furnace is equipped with manual reset limit switches in

the gas control area. The switches open and shut off power

to the gas valve if a flame roll--out or overheating condition

occurs in the gas control area. DO NOT bypass the

switches. Correct problem before resetting the switches.

!

WARNING

1. Maintain 115--v wiring and ground. Improper polarity will

result in rapid flashing LED and no furnace operation.

2. Make thermostat wire connections at the 24--v terminal

block on the furnace control. Failure to make proper
connections will result in improper operation. (See Fig.

24.)

3. Gas supply pressure to the furnace must be greater than

4.5--in. wc (0.16 psig ) but not exceed 14--in. wc (0.5

psig).

CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care

and wear appropriate protective clothing, safety glasses and

gloves when handling parts and servicing furnaces.

CAUTION

!

4. Check all manual--reset switches for continuity.
5. Install blower compartment door. Door must be in place to

operate furnace.

6. Setup switch descriptions The 2 stage furnace has DIP

switches used to select thermostat staging and blower off
delay timings. For switch locations on Furnace control
board, See Fig. 34 and 58.

7. Setup switch descriptions -- See Table 10.

Step 2 — Start--Up Procedures

FIRE AND EXPLOSION HAZARD
Failure to follow this warning could cause personal injury,

death and/or property damage.
Never purge a gas line into a combustion chamber. Never

use matches, candles, flame, or other sources of ignition for

the purpose of checking leakage. Use a soap--and--water

solution to check for leakage.

!

WARNING

1. Purge gas lines after all connections have been made.
2. Check gas lines for leaks.

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury, or death. Blower access door switch opens 115--v

power to control. No component operation can occur unless

switch is closed. Caution must be taken when manually

closing this switch for service purposes.

!

WARNING

3. To Begin Component Self--Test:

Remove blower access door. Disconnect the thermostat R
lead from furnace control board. Manually close blower
door switch. Short (jumper) the COM--24v terminal on

control to the TEST/TWIN 3/16--inch quick--connect
terminal on control until the LED goes out (approximately

2 sec). Gas valve and humidifier will not be turned on.
Remove jumper from terminals. (See Fig. 34 and Table

10.)

NOTE: The furnace control allows all components, except the
gas valve, to be run for short period of time. This feature helps
diagnose a system problem in case of a component failure.
Component test feature will not operate if any thermostat signal is
present at the control.
Refer to service label attached to furnace or See Fig. 57.
Component test sequence is as follows:

a. LED will display previous status code 4 times.

b. Inducer motor starts on high--speed and continues to run

until Step g of component test sequence.

c. Hot surface igniter is energized for 15 sec., then off.

d. Blower motor operates on LO--HEAT speed for 10 sec.

e. Blower motor operates on HI--HEAT speed for 10 sec.

f. Blower motor operates on COOL speed for 10 sec.

g. Inducer motor goes to low--speed for 10 sec., then stops.
h. Reconnect R lead to furnace control board, remove tape

from blower door switch and re--install blower door.

4. Operate furnace per instruction on inner door.
5. Verify furnace shut down by lowering thermostat setting

below room temperature.

6. Verify furnace restarts by raising thermostat setting above

room temperature.