Fig. 50 -- Rounded End of Knockout

A04129

Fig. 51 -- Knockout Pulled Loose

A04130

Fig. 52 -- Hammer and Screwdriver Used for Knockout

A04131

Fig. 53 -- Remove Knockout with Hammer

BURN HAZARD
Failure to follow this caution may cause personal injury.
Hot vent pipe is within reach of small children when

installed in downflow position.
See the following instruction.

CAUTION

!

An accessory Vent Guard Kit, KGAVG0101DFG is REQUIRED

for downflow applications for use where the vent exits through

the lower portion of the furnace casing door. Refer to the Vent
Guard Kit Instructions for complete details.
The horizontal portion of the venting system shall slope upwards
not less than 1/4--in. per linear ft (21 mm/m) from the furnace to

the vent and shall be rigidly supported every 5 ft or less with

metal hangers or straps to ensure there is no movement after
installation.
SIDEWALL VENTING
This furnace is not approved for direct sidewall horizontal

venting.
In the U.S.: Per section 10.3.4 of the NFGC, any listed

mechanical venter may be used, when approved by the authority

having jurisdiction.