Introduction – Bryant 2-stage Deluxe Induced-Combustion 4-way Multipurpose 120 User Manual

Page 3

Advertising
background image

3

Table 1 – Dimensions (In.)

FURNACE SIZE

A

CABINET

WIDTH

(IN.)

D

SUPPLY---AIR

WIDTH (IN.)

E

RETURN---AIR

WIDTH (IN.)

F

C.L. TOP AND

BOTTOM FLUE

COLLAR (IN.)

FLUE

COLLAR*

(IN.)

SHIP WT. (LB)

FILTER

MEDIA

CABINET

SIZE (IN.)

045---08/024045

14---3/16

12---9/16

12---11/16

9---5/16

4

116

16

045---12/036045

14---3/16

12---9/16

12---11/16

9---5/16

4

119

16

070---08/024070

14---3/16

12---9/16

12---11/16

9---5/16

4

120

16

070---12/036070

14---3/16

12---9/16

12---11/16

9---5/16

4

124

16

070---16/048070

17---1/2

15---7/8

16

11---9/16

4

138

16

090---14/042090

17---1/2

15---7/8

16

11---9/16

4

136

16

090---16/048090

21

19---3/8

19---1/2

13---5/16

4

151

20

090---20/060090

21

19---3/8

19---1/2

13---5/16

4

156

20

110---12/036110

17---1/2

15---7/8

16

11---9/16

4

144

16

110---16/048110

21

19---3/8

19---1/2

13---5/16

4

158

20

110---22/066110

21

19---3/8

19---1/2

13---5/16

4

163

20

135---16/048135

21

19---3/8

19---1/2

13---5/16

4†

163

20

135---22/066135

24---1/2

22---7/8

23

15---1/16

4†

174

24

155---20/060155

24---1/2

22---7/8

23

15---1/16

4†

181

24

* 5” or 6” vent connector may be required in some cases.
{

135 and 155 size furnaces require five---inch or larger vents. Use a 4---5 or 4---6 inch vent adapter between furnace and vent connector.

product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,

or operation.

1. Use only with type of gas approved for this furnace. Refer

to the furnace rating plate 2. Install this furnace only in a

2. Install this furnace only in a location and position as

specified in the “Location” section of these instructions.

3. Provide adequate combustion and ventilation air to the

furnace space as specified in “Air for Combustion and
Ventilation” section.

4. Combustion products must be discharged outdoors.

Connect this furnace to an approved vent system only, as
specified in the “Venting” section of these instructions.

5. Never test for gas leaks with an open flame. Use a

commercially available soap solution made specifically for
the detection of leaks to check all connections, as specified

in the “Gas Piping” section.

6. Always install furnace to operate within the furnace’s

intended temperature--rise range with a duct system which
has an external static pressure within the allowable range,
as specified in the “Start--Up, Adjustments, and Safety

Check” section. See furnace rating plate.

7. When a furnace is installed so that supply ducts carry air

circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled

by duct(s) sealed to the furnace casing and terminating
outside the space containing the furnace. See “Air Ducts”
section.

8. A gas--fired furnace for installation in a residential garage

must be installed as specified in the warning box in the

“Location” section.

9. The furnace may be used for construction heat provided

that the furnace installation and operation complies with

the first CAUTION in the LOCATION section of these
instructions.

10. These Multipoise Gas--Fired Furnaces are CSA (formerly

A.G.A. and C.G.A.) design--certified for use with natural

and propane gases (see furnace rating plate) and for
installation in alcoves, attics, basements, closets, utility
rooms, crawlspaces, and garages. The furnace is

factory--shipped for use with natural gas. A CSA (A.G.A.
and C.G.A.) listed accessory gas conversion kit is required

to convert furnace for use with propane gas.

11. See Fig. 2 for required clearances to combustible

construction.

12. Maintain a 1--in. clearance from combustible materials to

supply air ductwork for a distance of 36 inches
horizontally from the furnace. See NFPA 90B or local

code for further requirements.

13. These furnaces SHALL NOT be installed directly on

carpeting, tile, or any other combustible material other
than wood flooring. In downflow installations, factory
accessory floor base MUST be used when installed on

combustible materials and wood flooring. Special base is
not required when this furnace is installed on

manufacturer’s Coil Assembly Part No. CD5 or CK5, or
when Coil Box Part No. KCAKC is used. See Fig. 2 for
clearance to combustible construction information.

INTRODUCTION

The Series 120/C 4--way multipoise Category I fan--assisted
furnace is CSA (formerly A.A.A.. and C.G.A.) design--certified.

A Category I fan--assisted furnace is an appliance equipped with

an integral mechanical means to either draw or force products of
combustion through the combustion chamber and/or heat

exchanger. The furnace is factory--shipped for use with natural
gas. This furnace is not approved for installation in mobile

homes, recreational vehicles, or outdoors.
These furnaces shall not be installed directly on carpeting, tile, or

any other combustible material other than wood flooring. For

downflow installations, a factory accessory floor base must be
used when installed on combustible materials and wood flooring.

This special base is not required when this furnace is installed on
the manufacturer’s coil assembly, or when the manufacturer’s coil

box is used. See Fig. 2 for clearance to combustible material

information.
This furnace is designed for minimum continuous return--air

temperature of 60_F db or intermittent operation down to 55_F
db such as when used with a night setback thermostat. Return--air

temperature must not exceed 80_F db. Failure to follow these

return--air temperature limits may affect reliability of heat
exchangers, motors, and controls. (See Fig. 3.)
For accessory installation details, refer to the applicable
instruction literature.
NOTE: Remove all shipping brackets and materials before
operating the furnace.

312A

Advertising