Table 16 -- Orifice Size and Manifold Pressure for Gas Input Rate (cont.)

(Tabulated Data Based on 21,000 Btuh High--Heat/14,500 Btuh for Low--Heat Per Burner, Derated 4% for Each 1000 Ft Above

Sea level)

ALTITUDE RANGE

(FT)

AVG. GAS

HEAT VALUE

AT ALTITUDE

(BTUH/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

6001 to

7000

675

44

3.5/1.7

43

3.2/1.5

43

3.3/1.6

43

3.4/1.6

700

44

3.3/1.6

44

3.4/1.6

44

3.5/1.7

43

3.2/1.5

725

45

3.7/1.8

45

3.8/1.8

44

3.3/1.6

44

3.4/1.6

750

46

3.6/1.7

46

3.8/1.8

45

3.7/1.8

45

3.8/1.8

775

46

3.4/1.6

46

3.5/1.7

46

3.6/1.7

46

3.8/1.8

800

47

3.6/1.7

47

3.8/1.8

46

3.4/1.6

46

3.5/1.7

825

47

3.4/1.6

47

3.5/1.7

47

3.6/1.7

47

3.8/1.8

850

48

3.7/1.7

48

3.8/1.8

47

3.4/1.6

47

3.5/1.7

ALTITUDE RANGE

(FT)

AVG. GAS

HEAT VALUE

AT ALTITUDE )

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

7001 to

8000

650

44

3.3/1.6

44

3.4/1.6

44

3.5/1.7

43

3.2/1.5

675

45

3.7/1.8

45

3.8/1.8

44

3.3/1.6

44

3.4/1.6

700

46

3.6/1.7

46

3.7/1.8

46

3.8/1.8

45

3.8/1.8

725

47

3.8/1.8

46

3.5/1.7

46

3.6/1.7

46

3.7/1.8

750

47

3.5/1.7

47

3.7/1.8

47

3.8/1.8

46

3.5/1.6

775

48

3.8/1.8

47

3.4/1.6

47

3.6/1.7

47

3.7/1.7

800

48

3.6/1.7

48

3.7/1.8

48

3.8/1.8

47

3.4/1.6

825

48

3.3/1.6

48

3.5/1.6

48

3.6/1.7

48

3.7/1.8

ALTITUDE RANGE

(FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

8001 to

9000

625

45

3.7/1.8

45

3.8/1.8

44

3.3/1.6

44

3.4/1.6

650

46

3.6/1.7

46

3.7/1.8

46

3.8/1.8

45

3.8/1.8

675

47

3.8/1.8

46

3.4/1.6

46

3.5/1.7

46

3.7/1.7

700

47

3.5/1.7

47

3.6/1.7

47

3.7/1.8

46

3.4/1.6

725

48

3.7/1.8

48

3.8/1.8

47

3.5/1.7

47

3.6/1.7

750

48

3.5/1.7

48

3.6/1.7

48

3.7/1.8

48

3.8/1.8

775

49

3.8/1.8

48

3.4/1.6

48

3.5/1.7

48

3.6/1.7

ALTITUDE RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

9001 to

10,000

600

46

3.6/1.7

46

3.7/1.8

46

3.8/1.8

45

3.7/1.8

625

47

3.7/1.8

47

3.8/1.8

46

3.5/1.7

46

3.6/1.7

650

47

3.4/1.6

47

3.6/1.7

47

3.7/1.8

47

3.8/1.8

675

48

3.6/1.7

48

3.8/1.8

47

3.4/1.6

47

3.5/1.7

700

48

3.4/1.6

48

3.5/1.7

48

3.6/1.7

48

3.7/1.8

725

49

3.7/1.8

49

3.8/1.8

48

3.4/1.6

48

3.5/1.7

* Orifice numbers 43 are factory installed

SERVICE AND MAINTENANCE

PROCEDURES

FIRE, PERSONAL INJURY AND UNIT DAMAGE

HAZARD
Failure to follow this warning could result in personal injury,

death and/or property damage.
The ability to properly perform maintenance on this

equipment requires certain knowledge, mechanical skills,

tools, and equipment. If you do not possess these, do not

attempt to perform any maintenance on this equipment other

than those procedures recommended in the User’s Manual.

!

WARNING

ELECTRICAL SHOCK, FIRE OR EXPLOSION

HAZARD
Failure to follow this warning could result in personal injury

or death, or property damage.
Before servicing, disconnect all electrical power to furnace.

Verify proper operation after servicing.

!

WARNING