Caution – Bryant 2-stage Deluxe Induced-Combustion 4-way Multipurpose 120 User Manual

Page 33

Advertising
background image

33

Caution!! For the following applications, use the minimum vertical heights as specified below.

For all other applications, follow exclusively the National Fuel Gas Code

FURNACE

ORIENTATION

VENT ORIENTA-

TION

FURNACE IN-

PUT(BTUH/HR)

MINIMUM VENT

DIAMETER (IN.)*

MINIMUM VERTICAL VENT

HEIGHT (FT)**

Downflow

Vent elbow left, then

up Fig. 40

154,000

132,000

110,000(036/---12 only)

5

12

Horizontal Left

Vent elbow right,

then up Fig. 43

154,000

132,000

5

7

Horizontal Left

Vent Elbow up Fig.

44

154,000

132,000

5

7

Horizontal Left

Vent elbow right Fig.

45

154,000

5

7

Downflow

Vent elbow up then

left Fig. 38

110,000 (036/---12 only)

5

10

Downflow

Vent elbow up, then

right Fig. 41

110,000 (036/---12 only)

5

10

NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC. *4 in. inside casing or vent guard **Including 4 in. vent

section(s)

A04127

Fig. 49 -- Using Tin Snips to Cut Tie Points

CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care

and wear appropriate protective clothing, safety glasses and

gloves when handling parts and servicing furnaces.

CAUTION

!

NOTE: Vent connector length for connector sizing starts at
furnace vent elbow. The 4 inch vent elbow is shipped for upflow
configuration and may be rotated for other positions. Remove the
3 screws that secure vent elbow to furnace, rotate furnace vent
elbow to position desired, re--install screws. The factory--supplied
vent elbow does NOT count as part of the number of vent
connector elbows.
The vent connector can exit the door through one of 5 locations

on the door.

1. Attach the single wall vent connector to the furnace vent

elbow, and fasten the vent connector to the vent elbow
with at least two field--supplied, corrosion--resistant, sheet

metal screws located 180_ apart.

NOTE:

An accessory flue extension KGAFE0112UPH is

available to extend from the furnace elbow to outside the furnace
casing. If flue extension is used, fasten the flue extension to the
vent elbow with at least two field--supplied, corrosion--resistant,
sheet metal screws located 180_ apart. Fasten the vent connector

to the flue extension with at least two field--supplied, corrosion
resistant sheet metal screws located 180_ apart.

2. Vent the furnace with the appropriate connector as shown

in Fig. 36--48.

3. Orient the door to determine the correct location of the

door knockout to be removed.

4. Remove the correct U--shaped knockout in door.

NOTE: A number of techniques can be used to remove these
knockouts as seen in Fig. 49 through 53. The knockout in the
bottom of the door is unique due to its flanging and is more easily
removed by first cutting the two tie points at the edge of the door,
using aviation--type tin snips. (See Fig. 49.) A sharp blow to the
rounded end of the knockout (See Fig. 50.) will separate more tie
points and allow the knockout to be pulled loose. (See Fig. 51.)
Remove all burrs any sharp edges.
For the rectangular J--box knockout, use tin snips along the door

edge and use a sharp blow with a hammer to remove the
knockout. Remove any burrs and sharp edges.
For the knockouts in the other locations on the door (top and

sides), tin snips can also be used along the door edges; however,
the preferred method is to use a hammer and screwdriver to strike

a sharp blow (See Fig. 52.) directly to the knockout tie points or
use a hammer in the upper left corner of the desired knockout.

(See Fig. 53.) Remove any burrs and sharp edges.
NOTE: If a knockout does not come out after two sharp blows,
pull and snip as needed to remove the knockout. Additional
blows may cause damage to the door.

312A

Advertising