Table 10 – 2--Stage Furnace Setup Switch Description

SETUP

SWITCH NO.

SWITCH

NAME

NORMAL

POSITION

DESCRIPTION

OF USE

SW---1

Adaptive Heat Mode

OFF

When OFF, allows 2---stage operation with a single stage thermostat.

Turn ON when using 2 stage thermostat to allow Low Heat opera---

tion when R to W/W1 closes and High Heat operation when R to

W/W1 and W2 close.

SW---2

Blower OFF delay

ON or OFF

Control blower OFF delay time. Used in conjunction with SW---3.

See Table 14.

SW---3

Blower OFF delay

ON or OFF

Control blower OFF delay time. Used in conjunction with SW---2.

See Table 14.

Step 3 — Adjustments

FIRE HAZARD
Failure to follow this warning could result in injury, death

and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw.

This can result in unregulated manifold pressure and result

in excess over--fire and heat exchanger failures.

!

WARNING

FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace

life.
DO NOT re--drill orifices. Improper drilling (burrs, out--of

round holes, etc.) can cause excessive burner noise and

misdirection of burner flames. This can result in flame

impingement of heat exchangers, causing failures. (See Fig.

50.)

CAUTION

!

Furnace gas input rate on rating plate is for installations at

altitudes up to 2000 ft Furnace input rate must be within +/--2%
of furnace rating plate input. For altitudes above 5500 ft, a

field--supplied high altitude pressure switch is required.

1. Determine the correct gas input rate.

In the U.S.:
The input rating for altitudes above 2,000 ft must be re-

duced by 4% for each 1,000 ft above sea level.
For installations below 2000 ft, refer to the unit rating

plate.
For installations above 2000 ft, multiply the input on the

rating plate by the derate multiplier in Table 11 for the cor-
rect input rate.

EXAMPLE:
88,000 BTUH INPUT FURNACE INSTALLED AT 4300 FT

Derate

Furnace Input Rate

Furnace Input Rate

X

Multiplier

=

at Installation

at Sea Level

Factor

Altitude

88,000

X

0.90

=

79,200

In Canada: The input rating must be reduced by 10% for

altitudes of 2,000 ft to 4,500 ft above sea level by an
authorized Gas Conversion Station or Dealer. To

determine correct input rate for altitude, see example and

use 0.90 as derate multiplier factor.

2. Determine the correct orifice and manifold pressure

adjustment. All models in all positions except Low NOx

models in downflow and horizontal positions use Table 15
(22,000 BTUH per burner).

Table 11 – Altitude Derate Multiplier for U.S.A.

ALTITUDE

(FT)

%

OF DERATE

DERATE MULTIPLIER

FACTOR*

0–2000

0

1.00

2001–3000

8–12

0.90

3001–4000

12–16

0.86

4001–5000

16–20

0.82

5001–6000

20–24

0.78

6001–7000

24–28

0.74

7001–8000

28–32

0.70

8001–9000

32–36

0.66

9001–10,000

36–40

0.62

* Derate multiplier factors are based on midpoint altitude for altitude

range.

Low NOx models in downflow or horizontal positions MUST

use Table 16 (21,000 BTUH per burner). See input listed on

rating plate.

a. Obtain average yearly gas heat value (at installed altitude)

from local gas supplier.

b. Obtain average yearly gas specific gravity from local gas

supplier.

c. Find installation altitude in Table 15 or 16.

d. Find closest natural gas heat value and specific gravity

in Table 15 or 16

e. Follow heat value and specific gravity lines to point of

intersection to find orifice size and low--and high--heat
manifold pressure settings for proper operation.

f. Check and verify burner orifice size in furnace. NEVER

ASSUME ORIFICE SIZE. ALWAYS CHECK AND
VERIFY.

g. Replace orifice with correct size, if required by Table 15

or 16. Use only factory--supplied orifices. See
EXAMPLE 2.

EXAMPLE 2: (0--2000 ft altitude)
For 22,000 Btuh per burner application, use Table 15.
Heating value = 1000 Btuh/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 43*
Manifold pressure: 3.7--in. wc for high--heat
1.6--in. wc for low--heat
* Furnace is shipped with No. 43 orifices. In this example
all main burner orifices are the correct size and do not need
to be changed to obtain proper input rate.

3. Adjust manifold pressure to obtain low fire input rate. (See

Fig. 54.)

312A