Table 14 – 2--Stage Furnace Blower OFF delay Setup Switch

DESIRED HEATING MODE

BLOWER OFF DELAY (SEC.)

SETUP SWITCH

SW---2

SETUP SWITCH

SW---3

90

OFF

OFF

120

OFF

ON

150

ON

OFF

180

ON

ON

R Y W G

10 TURNS

THERMOSTAT SUBBASE

TERMINALS WITH

THERMOSTAT REMOVED

(ANITICIPATOR, CLOCK, ETC.,

MUST BE OUT OF CIRCUIT.)

HOOK-AROUND

AMMETER

EXAMPLE: 5.0 AMPS ON AMMETER

10 TURNS AROUND JAWS

= 0.5 AMPS FOR THERMOSTAT

ANTICIPATOR SETTING

FROM UNIT 24-V

CONTROL TERMINALS

A96316

Fig. 56 -- Amp. Draw Check with Ammeter

Step 4 — Check Safety Controls

The flame sensor, gas valve, and pressure switch were all checked

in the Start--up procedure section as part of normal operation.

1. Check Main Limit Switch(es)

This control shuts off combustion system and energizes
air--circulating blower motor, if furnace overheats. By
using this method to check limit control, it can be

established that limit is functioning properly and will
operate if there is a restricted return--air supply or motor

failure. If limit control does not function during this test,
cause must be determined and corrected.

a. Run furnace for at least 5 minutes.

b. Gradually block off return air with a piece of cardboard

or sheet metal until the limit trips.

c. Unblock return air to permit normal circulation.

d. Burners will re--light when furnace cools down.

2. Check draft safeguard switch.

The purpose of this control is to cause the safe shutdown
of the furnace during certain blocked vent conditions.

a. Verify vent pipe is cool to the touch.

b. Disconnect power to furnace and remove vent connector

from furnace vent elbow.

c. Restore power to furnace and set room thermostat above

room temperature.

d. After normal start--up, allow furnace to operate for 2

minutes, then block vent elbow in furnace 80% of vent

area with a piece of flat sheet metal.

e. Furnace should cycle off within 2 minutes. If gas does not

shut off within 2 minutes, determine reason draft

safeguard switch did not function properly and correct
condition.

f. Remove blockage from furnace vent elbow.

g. Switch will auto--reset when it cools.
h. Re--install vent connector.

NOTE: Should switch remain open longer than 3 minutes,
furnace control board will lockout the furnace for 3 hours. To
reset furnace control board, turn thermostat below room
temperature or from HEAT to OFF and turn 115--v power OFF,
then back ON.

3. Check Pressure Switch(es)

This control proves operation of the draft inducer blower.

a. Turn off 115--v power to furnace.

b. Disconnect inducer motor lead wires from wire harness.

c. Turn on 115--v power to furnace.

d. Set thermostat to “call for heat” and wait 1 minute. When

pressure switch is functioning properly, hot surface
igniter should NOT glow and control diagnostic light

flashes a status code 32. If hot surface igniter glows when
inducer motor is disconnected, shut down furnace

immediately.

e. Determine reason pressure switch did not function

properly and correct condition.

f. Turn off 115--v power to furnace.

g. Reconnect inducer motor wires, replace outer door, and

turn on 115--v power.

h. Blower will run for 90 seconds before beginning the call

for heat again.

i. Furnace should ignite normally.