IDEX Health & Science VS-606V7 Series User Manual

Page 100

Advertising
background image

100

Register No.

bit

Description

002AH

A

larm

Cont

ent

s

0

Operator stop (STP)

1

Sequence error (SER)

2

FWD - REV command simulation input (EF)

3

External baseblock (BB)

4

Overtorque detection (OL3)

5

Cooling fin overheat (OH)

6

Main circuit overvoltage (OV)

7

Main circuit undervoltage

8

Cooling fan fault (FAN)

9

Communication error

A

Option card communication error (BUS)

B

Not used

C

Inverter overheat prediction (OH3)

D

PID feedback loss (FBL)

E

Emergency stop (STP)

F

Communication waiting (CALL)

002BH

S

equ

enc

e i

n

put

0

Terminal S1

1 : Closed O : Open

1

Terminal S2

1 : Closed O : Open

2

Terminal S3

1 : Closed O : Open

3

Terminal S4

1 : Closed O : Open

4

Terminal S5

1 : Closed O : Open

5

Terminal S6

1 : Closed O : Open

6

Terminal S7

1 : Closed O : Open

7-F

(Not Used)

002CH

In

v

e

rt

er s

tat

us

0

Run

1 : Run

1

Zero - speed

1 : Zero - speed

2

Frequency agreed

1 : Agreed

3

Minor fault (Alarm is indicated)

4

Frequency detection 1

1: Output frequency

(n095)

5

Frequency detection 2

1

:

Output frequency

(n095)

6

Inverter operation ready

1 : Ready

7

Undervoltage detection

1 : Under Voltage detection

8

Baseblock

1 : Inverter output base block

9

Frequency reference mode

1 : Other than communications
0 : Communications

A

Run command mode

1 : Other than communications
0 : Communications

B

Overtorque detection

1 : Detection or overtorque fault

C

(Not used)

D

Fault restart

E

Fault (Including MEMOBUS communications timeover)

1 : Fault

F

MEMOBUS communications timeover 1 : Timeover

002DH

0

MA “ON”

1 : Closed 0 : Open

1

P1 “ON”

1 : Closed 0 : Open

2

P2 “ON”

1 : Closed 0 : Open

3-F

(Not used)