IDEX Health & Science VS-606V7 Series User Manual

Page 62

Advertising
background image

62

Input / Output Open Phase Protection

*1 0% setting - no detection

*2 0.0 sec setting - no detection

Recommended set values: 7% for n166

10sec. for n167

5% for n168

0.2sec. for n169

Parameters

No.

Name

Unit

Setting

Range

Initial

Setting

n166

Input open-phase

detection level

1%

0 to 100% *1

400.0V/100%

(for 200V class)

800.0V/100%

(for 400V class)

0%

n167

Input open-phase

detection time

1 sec.

0 to 255 sec. *2

0 sec.

n168

Output open-phase

detection level

1%

0 to 100% *1

Inverter rated output

current value/100%

0%

n169

Output open-phase

detection time

0.1 sec.

0.0 to 2.0 sec *2

0.0 sec.

Advertising