135

Protective
Operation

Output is shut
OFF and motor
coasts to a
stop.

RH (Installed type braking
resistor overheating)

The protection function has
operated.

• The declaration time

is too short.

• The regenerative

energy from the
motor is too large.

• Increase the

deceleration time.

• Reduce the

regenerative load.

(Internal Braking Transistor
Fault)
The braking transistor is not
operating properly.

• Replace the Inverter

OL1 (Motor overload)
Motor overload protection
operates by built-in electronic
thermal overload relay.

• Check the load size

or V/f pattern setting
(parameters n011 to
n017)

• Set the motor rated

current shown on the
nameplate by
parameter n036.

OL2 (Inverter overload)
Inverter overload protection
operates by built-in electronic
thermal overload relay.

• Check the load size

or V/f pattern setting
(parameters n011 to
n017)

• Check the inverter

capacity

OL3 (Over torque detection)
V/f mode: Inverter output

current exceeded the
preset value in
parameter n098.

Vector mode: Motor current or

torque exceeded the
preset value in
parameters n097 and
n098.

When over torque is detected,
inverter performs operation
according to the preset setting
of parameter n096.

Check the driven
machine and correct
the cause of the fault,
or increase the value of
parameter n098 up to
the highest value
allowed for the
machine.

Alarm Display

Inverter

Status

Explanation

Causes and

Corrective Actions

Digital

Operator

RUN (Green)

ALARM (Red)