084

0154

Jump frequency 2

0.00 to

400.0Hz

0.01Hz (less

than 100Hz) /
0.1Hz (100Hz

or more)

0.00Hz

60

085

0155

Jump frequency 3

0.00 to

400.0Hz

0.01Hz (less

than 100Hz) /
0.1Hz (100Hz

or more)

0.00Hz

60

086

0156

Jump frequency width

0.00 to

25.50Hz

0.01Hz

0.00Hz

60

087

0157

Cumulative operation
time selection (Note 9)

0.1

1

0

61

088

0158

Cumulative operation

0 to 6550

1=10H

0H

61

089

0159

DC injection braking
current

0 to 100%

1%

50%

72

090

015A

DC injection braking time
at stop

0.0 to 25.5%

0.1s

0.0s (Note 2)

72

091

015B

DC injection braking time
at start

0.0 to 25.5%

0.1s

0.0s

---

092

015C

Stall prevention (current
limit) during decel

0,1

1

0

88

093

015D

Stall prevention (current
limit) during accel

30 to 200%

1%

170%

86

094

015E

Stall prevention (current
limit) during running

30 to 200%

1%

160%

87

095

015F

Frequency detection
level

0.00 to

400.0Hz

0.01Hz (less

than 100Hz) /
0.1Hz (100Hz

or more)

0.00Hz

59

096

0160

Overtorque detection 1

0 to 4

1

0

58

097

0161

Overtorque detection 2

0.1

1

0

58

098

0162

Overtorque detection
level

30 to 200%

1%

160%

58

099

0163

Overtorque detection
time

0.1 to 10.0s

0.1s

0.1s

58

100

0164

Memory selection of hold
output frequency

0,1

1

0

77

101

0165

Speed search detection
time (Note 9)

0.1 to 10.0s

0.1s

0.2s

---

102

0166

Speed search operation
level (Note 9)

0 to 200%

1%

150%

---

103

0167

Torque compensation
gain

0.0 to 2.5

0.1

1.0

42

104

0168

Time parameter at
torque compensation

0.0 to 25.5s

0.1s

0.3s

42

105

0169

Torque compensation
iron loss

0.0 to 6550

0.01W (less

than 100W) /

1W (1000W or

more)

(Note 3)

42

106

016A

Motor rated slip

0.0 to 20.0Hz

0.1Hz

(Note 3)

44

No.

Register

No. for

Trans-

mission

Name

Setting Range

Setting

Unit

Initial

Setting