Writes the parameters stored inside the digital operator in batch to the inverter. Write-in is
possible only for the inverters with the same product series, power supply specifications and
control mode (V/f control or vector control).
Therefore, writing from 200 V class to 400 V class (or visa versa), from VS-606V7 to VSmini
J7 are not possible.
Parameter Copy Function Selection (n176), Parameter Read Prohibited Selection (n177),
Fault history (n178), Inverter Software No. (n179), and hold output frequency are not written.

Following parameters are not written if the inverter capacity is different.

[Example] Write the parameters from EEROM inside the digital operator to the inverter

Copy Function

Parameter No.

Name

Parameter No.

Name

n011 to n017

V/f setting

n108

Motor leakage inductance

n036

Motor rated current

n109

Torque compensation voltage

limiter

n080

Carrier frequency

n110

Motor no-load current

n105

Torque compensation iron loss

n140

Energy-saving coefficient K2

n106

Motor rated slip

n158

Motor code

n107

Motor resistance for one phase

Explanation

Operator display

• Enable the setting of the

parameters n001 to n179.

• Execute write-in (COPY) by

Parameter Copy Function
Selection (n176).

• Press DSPL to light [PRGM].

• Press ENTER to display the set

value.

• Change the set value to 4 by

pressing

or

key.

• Press ENTER.

• Change the parameter No. to

n176 by pressing

or

key.

• Press ENTER to display the set

value.

• Change the set value to CPy by

pressing

or

key.

• Press ENTER.

• Press DSPL or ENTER

(Can be a different parameter No.)

( Lit )

(Can be a different set value.)

(Blinks)

(Lit for one second.)

(The parameter No. is
displayed)

( Lit )

(Lit)

(Blinks while executing CPY)

(End is displayed after the

execution of CPY is completed.)

(The parameter No. is

displayed.)