IDEX Health & Science VS-606V7 Series User Manual

Page 55

Advertising
background image

55

n018 setting

Notes: Parameter n018 can be set during stop.
If the numeric value exceeded 600.0 sec. is set for the accel/decel time when n018 = 0 (in units
of 0.1 sec.). “1” cannot be set to n018.

Accel time
Set the time needed for output frequency to reach 100% from 0%.

Decel time
Set the time needed for output frequency to reach 0% from 100%.

(Maximum output frequency n011 = 100%)

When parameter n081 is set to 1 or 2, operation automatically restarts even if
momentary power loss occurs.

* Hold the operation command to continue the operation after recovery from a momentary power

loss.

= When 2 is selected, the inverter restarts if power supply voltage recovers while the control power

supply is held.
No fault signal is output.

No.

Name

Unit

Setting Range

Initial setting

n019

Accel time 1

Refer to

n018

setting

Refer to n018

setting

10.0s

n020

Decel time 1

10.0s

n021

Accel time 2

10.0s

n022

Decel time 2

10.0s

No.

Unit

Setting Range

n018

0

0.1s

0.0 - 999.9s (999.9s or less)

1s

1000 - 6000s (1000s or more)

1

0.01s

0.00 - 99.99s (99.99s or less)

0.1s

100.0 - 600.0s (100s or more)

Automatic restart after momentary power loss (n081)

Setting.

Description

0

Continuous operation after momentary power loss not provided.

1*

Continuous operation after power recovery within momentary
power loss ride thru time 0.5s.

2*

=

Continuous operation after power recovery (Fault output not
provided)