Selects the function to be monitored at analog output terminals AM-AC.

In initial setting, analog voltage of approx. 10V is output when output frequency
(output current) is 100%.

Used to adjust analog output gain.

Set the analog output voltage at 100% of output frequency (output current). Frequency
meter displays 0 to 60Hz at 0 to 3V.

Using frequency meter or ammeter (n066)

Setting

Description

0

Output frequency

1

Output current

2

Main circuit DC voltage

3

Torque monitor

4

Output power

5

Output voltage reference

Calibrating frequency meter or ammeter (n067)

10V

n067 Setting

0.30

×

3V

=

Output frequency becomes

100% at this value