Chapter 7: IMS-4000 Sensors

Configuration

All IMS Solution sensors are auto-configured when you plug them into the Host or Node. When a new sensor is plugged

into the Host or Node, the configuration is set to the factory default via the Sensor Template. If you have modified these

templates, the configuration will be set to the modified configuration. When a sensor is removed, or the connection is dis-

rupted, the configuration data remains intact but the sensor will go into trouble status and generate a trouble alarm. When

the sensor is plugged in again, or the connection is re-established, configuration data remains unchanged and the sensor

returns to normal operating condition.

Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm. Removing or

unplugging a sensor for more than 60 seconds or plugging in a different sensor at any time will cause a trouble

alarm.

sensor Template (factory default)

specifications

Input Name: Contact Bridge

Bridge:

Recognition Time: 3 Seconds

Input: Normally Open or Normally Closed dry

contact

Reset Time: 0 Seconds

Source/Sense Voltage: 14VDC

Data Logging: Active

Source/Sense Current: 10mA

Voice: dry contact.wav

Cable/Connector: 7' cable with RJ-45 plug

Input Class: Other

Operating

Temperature Range: 32° to 122°F (0° to 50°C)

Housing: Black plastic

Dimensions: 2.13" x 0.6" x 1.38"

Door Switch

Normality: Normally Closed

Dimensions: 2.0" x 0.4" x 0.4" (with screw terminals)

Dimensions: 2.0" x 0.4" x 0.4" (part with magnet)