Ims-4812 mini temperature sensor – Sensaphone IMS-4000 Users manual User Manual

Page 98

Advertising
background image

IMS-4000 Manual

96

iMs-4812 Mini TeMperaTUre sensor

introduction

The IMS-4812 Mini Temperature Sensor is designed to connect to the IMS-4000 Host or Node and monitor temperatures in

tight locations (for example, inside equipment racks). The electrical connection between the sensor and IMS-4000 is made

via the attached RJ-45 patch cable. The sensor may be secured inside equipment using double-sided tape (included) or with

tie-wraps.

Cabling

The Mini-Temperature Sensor comes with an attached 7' cable with an RJ-45 plug on the end. If the sensor is close to the

IMS-4000 Host or Node, you can plug the sensor directly to an IMS environmental input. If the cable is too short you can

use the included RJ-45 adaptor and a longer patch cable to extend the length. For applications where the sensor may be far

from the IMS unit, you may utilize your existing network wiring infrastructure. For example, the sensor may be installed in

another room or another floor. Connect the sensor to your structured wiring network via an RJ-45 jack. At the other end,

connect a patch cable from your structured wiring patch panel directly to the Host or Node environment input.

Caution: The IMS sensors are not TCP/IP devices and therefore should not be connected directly to any wiring

infrastructure that is connected to network equipment as a hub, router, or switch. Sensors use RJ-45 plugs and

cables similar to those used with Ethernet devices.

Mounting

The temperature sensor may be mounted directly on a surface using double-sided tape (included) or it may be secured to

equipment using tie-wraps. The choice depends on your application.

Configuration

All IMS Solution sensors are auto-configured when you plug them into the Host or Node. When a new sensor is plugged

into the Host or Node, the configuration is set to the factory default via the Sensor Template. If you have modified these

templates, the configuration will be set to the modified configuration. When a sensor is removed, or the connection is dis-

rupted, the configuration data remains intact but the sensor will go into trouble status and generate a trouble alarm. When

the sensor is plugged in again, or the connection is re-established, configuration data remains unchanged and the sensor

returns to normal operating condition.

Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm. Removing or

unplugging a sensor for more than 60 seconds or plugging in a different sensor at any time will cause a trouble

alarm.

sensor Template (factory default)

specifications

Input Name: Temperature

Low Temperature Limit: 50ºF
High Temperature Limit: 85ºF

Recognition Time: 60 Seconds

Reset Time: 0 Seconds

Data Logging: Active

Voice: temperature.wav

Input Class: Temperature

Range: 5° to 140°F

Humidity: 5–90% RH

Sensor type: solid state ic

Accuracy: +/- 3 degrees F

Connector: 7' cable w/RJ-45 plug

Housing: black plastic

Housing dimensions: 2.13'' l x 0.6'' d x 1.38'' h