Chapter 2: IMS-4000 Software

Additionally, there is an option to re-dispatch the alarm if it remains in an alarm state too long. This programmable time

period is called the Alarm Reset Time. This parameter can be set from 30 to 3600 minutes. For example: Suppose the Alarm

Reset Time is set to 180 minutes. Now suppose an IP device has stopped responding and trips an alarm which results in all

programmed users receiving their respective messages. If the IP device continues to remain unresponsive for 180 minutes,

then the alarm will be dispatched again and everyone will be contacted once more.

Note: DO NOT set the Alarm Reset Time too short, otherwise you will continue to dispatch the same alarm

over and over resulting in numerous phone calls, e-mails, etc.

Figure 28: IP Alarm Flowchart

reMoVinG an ip alarM

Expand the IP Alarms and right-click on the IP Alarm you wish to remove. Choose Delete this IP Alarm, and it will be

removed.

inpUT/alarM Classes

Classes are used to associate environmental inputs and IP alarms with people. Each input sensor or IP address must be

assigned to a Class. Each person or User Profile selects classes for which they have responsibility. To view the list of Classes,