Chapter 2: Installation

21

CHAPTER 2: INSTALLATION

OPERATING ENVIRONMENT

The Sensaphone 1400 should be mounted and operated in a clean,
dry environment. The unit is microprocessor-controlled and as a
result it should not be installed near devices that generate strong
electromagnetic fields. Such interference is typically generated by
power switching equipment such as relays or contactors. A poor
operating environment may result in unwanted system resets and/or
system lockup. The temperature range the unit can operate in is
32°F to 122°F (0°C to 50°C). If the unit needs to operate below
freezing, a heater should be installed nearby.

Mounting the 1400

The NEMA-4 enclosure comes with hardware for wall or panel
mounting. The four tabs are attached by screwing the round bubble-
end of a tab to each of the four rear corners of the enclosure. Then
mount the unit in a position that allows easy access to the Zone
terminal block and keypad. Also, there must be a power outlet and
telephone jack close to the unit.

5 c”

118”

Figure 1: Mounting Dimensions