Sensaphone 1400 User Manual

Page 34

Advertising
background image

Sensaphone 1400 Manual

32

2. Press the CONFIGURE key.

The 1400 will prompt, “Enter 0 for automatic configuration, enter
zone number for manual configuration.” If you press “0”, the 1400
will scan each Zone input and determine the input type.

The Zones are now considered normal. If a normally closed Zone
becomes open, an alarm will occur. If a normally open Zone
becomes closed, an alarm will occur.

MANUAL ZONE CONFIGURATION

If you would like to program the Zone type (NO, NC, temperature,
4–20mA) without going through the automatic process that scans
all Zones, this command will allow you to configure a single Zone.
This command is useful if you have alarms on other channels and
cannot use the automatic configuration process, or if you wish to
configure the Zone type without actually connecting the sensor.

NOTE: You MUST use manual configuration for

any zone connecting to a 10K temperature sensor.

1. Press the SET key.

2. Press the CONFIGURE key.

The 1400 will prompt, “Enter 0 for automatic configuration, enter
zone number for manual configuration.”