Alarm limits – Sensaphone 1400 User Manual

Page 42

Advertising
background image

Sensaphone 1400 Manual

40

1. Press the WHAT IS key.

2. Press the REC TIME key.

1400 will say “Enter Zone Number.”

3. Press the corresponding Zone key (1–4), Power(0), or Sound

(9).

The 1400 will recite the programmed recognition time for that
Zone.

ALARM LIMITS

The Alarm Limits determine the level at which a temperature or
4–20mA Zone has reached the alarm threshold. The input value
must exceed the Alarm Limit to trip an alarm. Each Zone has a
programmable Low and High Alarm Limit. The default settings are
Low Limit=0 and High Limit=100. The range of programming for
2.8K thermistors is -109° to 115°F (-85° to 57°C). The range of
programming for 10K thermistors is -87° to 168°F (-66° to 76°C).
For zones configured as 4–20mA, the range of programming is
-10,000 to 10,000. To make a value negative, precede the value with
the [RINGS/TAD/*]

key.

NOTE: Only Zones configured as temperature or

4–20mA can have Alarm Limits programmed.