Chapter 4: Zone Programming

31

CHAPTER 4: ZONE PROGRAMMING

This chapter explains the keyboard commands for the monitoring
functions of the Sensaphone 1400. This includes:

Configure Zone Type
Enable/Disable Zones
Temperature Scale
Table Range for 4-20mA sensors
Alarm Recognition Time
Alarm Limits
Zone Calibration
AC Power Monitoring Enable/Disable
AC Power Recognition Time
Sound Level Monitoring Enable/Disable
Sound Level Recognition Time
Sound Level Calibration

AUTOMATIC ZONE CONFIGURATION

The 1400 is compatible with normally open, normally closed,
2.8K thermistor (temperature), 10K thermistor (temperature),
and 4-20mA type sensors. All of the Zones are configured
simultaneously by keying in a simple key sequence after connecting
all of your sensors. Make sure all sensors are in their normal state.
All 4–20mA transducers should be powered on.

NOTE: New temperature sensors will default con-

figure to 2.8K. If you are connecting any 10K

sensors to the 1400, these

must be configured man-

ually. Any sensor that was previously configured as

either 2.8K or 10K will maintain proper thermistor

type. (See the Manual Configuration section)

1. Press the SET key.