Rockwell Automation 1203 Serial Communications Module Series B User Manual

Page 16

Advertising
background image

2–2

Installation

1203–5.5 September 1995

Factory Switch Settings

The following table shows the switch settings that are set at the
factory:

Switch

Setting

Communication Mode

SW3–8

Off

Default application timeout disabled

SW3–7

Off

SW3–6

Off

Duplicate message detection disabled

SW3–5

Off

Datalink D disabled

SW3–4

Off

Datalink C disabled

SW3–3

Off

Datalink B disabled

SW3–2

Off

Datalink A disabled

SW3–1

Off

Logic command/status and

reference/feedback disabled

SW2–8

Off

BCC checksum

SW2–7

Off

Point–to–point

SW2–6

Off

1 stop bit

SW2–5

Off

Even parity (if enabled)

SW2–4

Off

Parity disabled

SW2–3

On

9600 baud

SW2–2

On

SW2–1

Off

SW1–8

Off

Module address = 1

SW1–7

Off

SW1–6

Off

SW1–5

Off

SW1–4

Off

SW1–3

On

SW1–2

Off

RS–232 (DF1 protocol)

SW1–1

Off

These switches can be visually represented as follows:

O

8 7 6 5 4 3 2 1

SW3

O

8 7 6 5 4 3 2 1

SW2

O

8 7 6 5 4 3 2 1

SW1