Fault queue entry read full, Plc block transfer emulation instruction data – Rockwell Automation 1203 Serial Communications Module Series B User Manual

Page 64

Advertising
background image

5–16

1203–5.5 September 1995

This function reads the contents of the specified fault queue entry. A
message is returned which includes the fault text and fault code
associated with the specified fault queue entry. The 1336 FORCE
also returns the time stamp associated with the fault.

PLC Block Transfer Emulation Instruction Data

PLC request instruction length: 3 words
Drive response instruction length: 12 or 16 words

Header

Word 1

PLC Decimal Value

1792

Message Structure

Header

Word 2

Header

Word 3

PLC Request

Header Word 1

Header Word 2

Data Word 3

Message Length

Message Length

PLC Decimal Value

Fault Queue

Drive Response

Fault Queue

3

Entry Number

18

Data

Word 4

Fault Text

Char 2

Char 1

Data

Word 5

Fault Text

Char 4

Char 3

Data

Word 6

Fault Text

Char 6

Char 5

Data

Word 7

Fault Text

Char 8

Char 7

Data

Word 8

Fault Text

Char 10

Char 9

Data

Word 9

Fault Text

Char 12

Char 11

Data

Word 10

Fault Text

Char 14

Char 13

Data

Word 11

Fault Text

Char 16

Char 15

1792 –– Message OK

–30976 –– Message Error

Entry Number

Data

Word 12

Fault Code Value

Data

Word 13

Clock Time

SES

REF

Data

Word 14

Clock Time

Hour

Minute

Data

Word 15

Clock Time

Date

Day

Data

Word 16

Clock Time

Year

Month

1336 FORCE

Drive Only

Fault Queue Entry Read
Full

Advertising