Configuration examples, Df1 messaging with a plc–5/80 example – Rockwell Automation 1203 Serial Communications Module Series B User Manual

Page 43

Advertising
background image

4–9

Configuring and Interfacing

1203–5.5 September 1995

DF1 Messaging with a PLC–5/80 Example

This example reads parameters 1 through 50.

Ladder rung example for Gx2 manual

Rung 2:0

| I:000 MG20:0 B3 +MSG––––––––––––––––––––+ |

+––] [–––]/[–––[ONS]––––––––––––––––––––––––––––+SEND/RECEIVE MESSAGE +–(EN)–+

| 00 EN 2 |Control block MG20:0+–(DN) |

| | +–(ER) |

| +–––––––––––––––––––––––+ |

Data Table Report

MESSAGE INSTRUCTION DATA MONITOR FOR CONTROL BLOCK MG20:0

Communication Command:

PLC–5 TYPED READ

PLC–5 Data Table Address:

N30:0

ignore if timed–out:

0 TO

Size in Elements:

50

to be retried:

0 NR

Local/Remote:

LOCAL

awaiting execution:

0 EW

Remote Station:

N/A

continuous:

0 CO

Link ID:

N/A

error:

0 ER

Remote Link Type:

N/A

message done:

0 DN

Local Node Address:

001

message transmitting:

0 ST

Destination Data Table Address:

N10:1

message enabled:

0 EN

Port Number:

00

Error Code: 0000 (HEX)

Configuration Examples