Fault clear/reset, Plc block transfer emulation instruction data, Message operation – Rockwell Automation 1203 Serial Communications Module Series B User Manual

Page 63

Advertising
background image

5–15

Block Transfer Emulation Instructions

1203–5.5 September 1995

The Fault Clear/Reset message activates the Clear Fault, Clear Fault
Queue, and Drive Reset functions.

PLC Block Transfer Emulation Instruction Data

PLC request instruction length: 4 words
Drive response instruction length: 4 words

Header

Word 1

PLC Decimal Value

–30976

Message Structure

Header

Word 2

Data

Word 3

PLC Request

Header Word 1

Header Word 2

Header Word 3

Message Length

PLC Decimal Value

1792 –– Message OK

–30976 –– Message Error

0

Drive Response

4

0

Data Word 4

Fault Command

Value

Fault Command

00
01
02
03

Not Used
Clear Fault
Clear Fault Queue
Drive Reset (1336 FORCE Only)

Message Length

4

Data

Word 4

Status Word

Message Operation

The specified fault Clear/Reset function sends a fault handling
request to the device.

A Clear Fault request clears the last fault that occurred.

A Clear Fault Queue clears the entire fault buffer. Certain
devices may store more than one fault.

A Drive Reset is used with the 1336 FORCE drive product only.
This function resets the drive; it clears the fault queue and writes
the parameter information stored in EEPROM to RAM.

Data File Format

4

–30976

* Example only – These values vary depending on parameters and products.

1,2,3

0

0

N10:0

1

2

3

4

5

6

7

8

9

PLC request

4

1792

0*

0

N90:0

Drive response

Fault Clear/Reset