Rockwell Automation 1203 Serial Communications Module Series B User Manual

Page 23

Advertising
background image

2–9

Installation

1203–5.5 September 1995

Use SW3–4 to enable and disable Datalink C messaging:

SW3

Function

O

8 7 6 5 4 3 2 1

Disable Datalink C messaging.

O

8 7 6 5 4 3 2 1

Enable Datalink C messaging.

Use SW3–5 to enable and disable Datalink D messaging:

SW3

Function

O

8 7 6 5 4 3 2 1

Disable Datalink D messaging.

O

8 7 6 5 4 3 2 1

Enable Datalink D messaging.

Use SW3–6 to enable and disable duplicate message detection:

SW3

Duplicate Message Detection

O

8 7 6 5 4 3 2 1

Disable duplicate message detection.

O

8 7 6 5 4 3 2 1

Enable duplicate message detection.

Use SW3–7 and SW3–8 to set the default application timeout value.
The default value is used for application timeout unless the user
writes a value to the application timeout address in the Serial
Communications Module data table. This address is N42:3. If
power is removed, the default value is reloaded during power–up.

SW3

Application Timeout Default Value

O

8 7 6 5 4 3 2 1

No timeout (disabled)

O

8 7 6 5 4 3 2 1

1 second

O

8 7 6 5 4 3 2 1

30 seconds

O

8 7 6 5 4 3 2 1

60 seconds

In DH–485 mode, the application timeout function is as follows:

If the application timeout is set to zero, the module will not cause
the SCANport device to fault if DH–485 communications are
disrupted.

If the application timeout is set to a non–zero value, the module
causes the SCANport device to fault if a DH–485 device that had
sent a message to data table N41 drops off the network.