7 - specifications, Chapter objectives, Module compatibility – Rockwell Automation 1203 Serial Communications Module Series B User Manual

Page 71: Specifications, Chapter, Chapter objectives module compatibility

Advertising
background image

Chapter

7

1203–5.5 September 1995

Specifications

This chapter provides you with background information and
specifications that you may need to install or apply your Serial
Communications Module.

Product Specifications

Open Style

Enclosed Style 115/230V

AC

Enclosed Style 24V DC

Catalog Number:

–GM2

–GD2

–GK2

Environmental:

Operating Temperature

0 to 50

°

C (32 to 122

°

F)

0 to 50

°

C (32 to 122

°

F)

0 to 50

°

C (32 to 122

°

F)

Storage Temperature

–40 to 85

°

C (–40 to 185

°

F)

–40 to 85

°

C (–40 to 185

°

F)

–40 to 85

°

C (–40 to 185

°

F)

Electrical:

Input Voltage

Supplied by drive

85 to 264V AC, 1 phase

24V DC,

±

10%

Input Frequency

NA

45 to 63 Hz

NA

Input Current

NA

35mA maximum

0.4 amps maximum

SCANport Load

60mA DC

60mA DC

60mA DC

Communications:

SCANport Side

SCANport Peripheral

Interface

SCANport Peripheral

Interface

SCANport Peripheral

Interface

Serial Side

RS–232/RS–422/RS–485

(DF1)

DH–485

RS–232/RS–422/RS–485

(DF1)

DH–485

RS–232/RS–422/RS–485

(DF1)

DH–485

Baud Rates

110, 300, 600, 1200, 2400,

4800, 9600, 19.2K

110, 300, 600, 1200, 2400,

4800, 9600, 19.2K

110, 300, 600, 1200, 2400,

4800, 9600, 19.2K

Checksum

BCC or CRC

BCC or CRC

BCC or CRC

Dimensions:

Open (IP00)

NEMA Type 1 (IP30)

NEMA Type 1 (IP30)

NA

45w x 76h x 123d mm

(1.8 x 3.0 x 4.8 in.)

45w x 76h x 123d mm

(1.8 x 3.0 x 4.8 in.)

This module is intended for use with devices that communicate via
RS–232, RS–422, or RS–485 hardware standards using the DF1
protocol or the DH–485 standard. The Serial Communications
Module is intended to provide a means for transmitting messages
between these serial communications devices and Allen-Bradley
SCANport devices.

Chapter Objectives

Module Compatibility

Advertising