5–6

1203–5.5 September 1995

The Product ID Number Read function returns the product ID of the
device to which the Serial Communications Module is connected.

PLC Block Transfer Emulation Instruction Data

PLC request instruction length: 3 words
Drive response instruction length: 4 words

Header

Word 1

PLC Decimal Value

256

Message Structure

Header

Word 2

Header

Word 3

PLC Request

Header Word 1

Header Word 2

Data Word 3

Message Length

Message Length

PLC Decimal Value

256 –– Message OK

–32512 –– Message Error

0

Drive Response

3

0

Product ID
Number

Description

2
3
4
5
16
17
18
19
20
21
22
23

1336F (PLUS Fractional)
1336F (PLUS)
1336G (FIBERS Fractional)
1336G (FIBERS)
1336T (FORCE)
1395
1394
1557
SMP
SMC
1304
1305

6

Data

Word 4

Product ID Number

Message Operation

The Product ID Number Read function, through the drive response
message word 4, indicates the type of device the Serial
Communications Module is connected to. This value is defined in
the message response chart shown above.

If an error has occurred, word 2 of the response returns a negative
value of –32512.

Product ID Number Read