Rockwell Automation 1203 Serial Communications Module Series B User Manual

Page 39

Advertising
background image

4–5

Configuring and Interfacing

1203–5.5 September 1995

The following is the data table structure for PLC–2 style addressing:

Parameter

Number

PLC–2 Style Address

Decimal (Octal)

Description of Location’s Purpose

1 – 7039

512 + Parm #

(1000 to 16577)

Parameter value read

(16600 to 167770

Status of last parameter write

1 – 7039

7680 + Parm #

(17000 to 34577)

Parameter read full

(34600 to 34677)

Block transfer emulation area

(34700)

Logic command/status

(34701)

Reference/feedback

(34702)

Datalink A1

(34703)

Datalink A2

(34704)

Datalink B1

(34705)

Datalink B2

(34706)

Datalink C1

(34707)

Datalink C2

(34710)

Datalink D1

(34711)

Datalink D2

(34712)

#ENQs

(34713)

#NAKs

(34714)

Message TIMEOUT (mS)

(34715)

Application TIMEOUT (seconds)

(34716)

Adapter series number (2=B)

(34717)

Adapter firmware version (201=FRN2.01)

(34720)

Maximum node address (DH–485)

(34721 to 37677)

Reserved area for future expansion

(37700 to 37777)

System area

Note: The address locations shown in this table are not limited to
PLC–2 commands and may be used by any device that can generate
them.

"