Installation and Wiring

Chapter 2

Wiring Diagrams

The wiring diagrams in this manual are drawn with European (IEC) conventions.

For convenience, a connection diagram is shown below in IEC style on the left

and in its corresponding NEMA style (used in the U.S.) on the right.

Figure 7 - Wiring Diagram Interpretation

These diagrams are simplified. Wiring of the power monitor must comply with

all applicable codes, standards, and regulations. Voltage and control power wiring

must be protected by suitable overcurrent protection. Connect current

transformer (CT) secondary wiring through a suitable shorting terminal block.

Figure 8 - System Type Selection: 3-phase.2, 3-phase, 2-wire, Balanced Load

Figure 9 - System Type Selection: 3-phase.n, 3-phase, 4-wire, Unbalanced Load

IMPORTANT

In these diagrams, ‘balanced load’ configurations permit 3-phase
measurement by using only one phase connection. Unbalance in the measured
circuit impacts the accuracy of the measurements.

1-CT and 1-VT/PT Connections

1-CT Connection

I1

I1

L1 N S1 S2

L1 N S1 S2

3-CT and 3-VT/PT Connections

3-CT Connection

I1

I2

I3

I1

I2

I3

L2

L1

L3 N

S1

S1

S2

S2

S1 S2

L2

L1

L3 N

S1

S1

S2

S2

S1 S2