Configuration flow chart – Rockwell Automation 1420 PowerMonitor 500 User Manual

Page 26

Advertising
background image

26

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013

Chapter 3

Unit Configuration

Configuration Flow Chart

10 CHANGE PAS: this function lets you modify the

PASS value with a new value (from 0…9999).

20 BACKLIGHT: adjusts backlight time from

0…255 minutes (0 = always on).

50 SYSTEM: this function lets you select the type of

electrical system.
Refer to pages

17

18

for descriptions and wiring

diagrams corresponding to the system type

designations, such as, 3P and 3P.n.

60 CT RATIO: this function lets you select the value

of the CT ratio (primary/secondary ratio of the

current transformer being used). Example: if the CT

primary (current transformer) has a current of 300 A

and the secondary a current of 5 A, the CT ratio

corresponds to 60 (300 divided by 5).

70 PT RATIO: this function lets you select the value

of the PT (VT) ratio (primary/secondary ratio of the

potential/voltage transformer being used). Example:

if the primary of the connected PT is 20 kV and the

secondary is 100V, then the PT ratio corresponds to

200 (20,000 divided by 100).