Configuration - base unit: read and write – Rockwell Automation 1420 PowerMonitor 500 User Manual

Page 55

Advertising
background image

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013

55

PowerMonitor 500 Unit Data Tables

Appendix A

Table 23 - Energy Metering Values Modbus - Read-only

Modbus

Address

Length

(words)

Description / Units

Data Format

Notes

301281

4

Total kWh+

ULINT

Values in Wh or varh

301285

4 Total

kVARh+

ULINT

301289 4 Total

kWh-

ULINT

301293 4

Total

kVARh-

ULINT

301297 4 Partial

kWh+

ULINT

301301

4 Partial

kVARh+

ULINT

301305 4 Partial

kWh-

ULINT

301309 4 Partial

kVARh-

ULINT

301313

4

Hours counter

ULINT

Hours value: integer part got from the division of the counter by
100 Minutes value: rest of the previous computation (decimal part)

Table 24 - Configuration - Base Unit: Read and Write

Modbus

Address

Length

(words)

Description / Units

Data Format

Notes

304097

1

Password

UINT

Minimum valid value: 0d Maximum valid value: 9999d

304098

1

Electrical system selection

UINT

Value =0: 1P (1-phase 2-wire) Value =1: 2P (2-phase 3-wire)
Value=2: 3P (3-phase 3-wire) Value=3: 3P2 (3-phase 2-wire) one
current and 1-phase (L1) to neutral voltage measurement)
Value=4: 3P1 (3-phase 4-wire one current and 3-phase to neutral
voltage measurements) Value=5: 3PN (default =3PN)

304099 1

Reserved

UINT

Value

=

5

304101

1

Backlight mode

UINT

The timing backlight is programmable from 0…255 minutes
(0 = always ON)

304107

1

DMD - Calculation

UINT

Selection of the DMD calculation mode Value=0: Fixed Value=1:
Slide - only for W

 and VA

304108

1

DMD - Time interval

UINT

Value=0: 1 min Value=1: 5 min Value=2: 10 min Value=3: 15 min
Value=4: 20 min Value=5: 30 min Value=6: 60 min

304110

1

DMD - Synchronisation

UINT

Synchronisation selection mode Value=0: OFF Value=1: Clock

304121

2

CT - Current transformer ratio

REAL

1.0…9999.0

304123

2

VT(PT) - Voltage transformer ratio

REAL

1.0…9999.0

304127

2

Filter Span parameter

REAL

Value min = 0.0
Value max = 100.0 (Disabled = 0.0)

304129

2

Filter Coefficient

REAL

Value min = 1.0
Value max = 256.0

304177

16

Virtual Alarm AL1 (LED 1)

Customized

Refer to the

Table 25

304193

16

Virtual Alarm AL2 (LED 2)

Base Alarm data structure

304209

16

Virtual Alarm AL3 (LED 3)

304225

16

Virtual Alarm AL4 (LED 4)