Rockwell Automation 1420 PowerMonitor 500 User Manual

Page 65

Advertising
background image

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013

65

Technical Specifications

Appendix B

Table 35 - Analog Output Specifications (A option)

Attribute

Value

Number of outputs

2

Accuracy (@ 25 °C ±5 °C, R.H.

60%)

± 0.2% of full scale

Range 0…20

mA

Configuration

By means of the front keypad

Signal retransmission

The signal output can be connected to any instantaneous variable. See

List of Connectable Variables on page 69

Scaling factor

Programmable within the whole range of retransmission; it allows the retransmission management of all values from
0…20 mA DC

Response time

400 ms typical (filter excluded)

Ripple

1% (according to IEC 60688-1, EN 60688-1)

Total temperature drift

500 ppm/°C

Load

600 

Insulation See

Table 42

Isolation Between Inputs and Outputs (1 minute)

Table 36 - Serial RS-485/RS-232 Communication Specifications (485 option)

Attribute

Value

RS-485/RS-422 port

Type Multidrop,

bidirectional

(static and dynamic variables)

Connections 2-wire max distance 1000 m, termination
directly on the module

Addresses

247, selectable by means of the front key-pad or through the software

Protocol Modbus

RTU

Data (bidirectional)

Dynamic (reading only)

System and phase variables: see the Modbus register maps

Static (reading and writing only)

All the configuration parameters; see the Modbus register maps

Data format

1 start bit, 8 data bit, no/even/odd parity,1 stop bit

Communication rate

Selectable: 9.6, 19.2, 38.4, 115.2 Kbps

Driver input capability

1/5 unit load. Max 160 transceivers on the same bus

Insulation See

Table 42

Isolation Between Inputs and Outputs (1 minute)

RS-232 port

Type Bidirectional

(static and dynamic variables)

Connections

3 wires. Max distance 15 m

Protocol Modbus

RTU