2. Click the Communication tab and enter the path and method.

3. Click OK to complete message setup.

Implicit Messaging - Generic Ethernet Module Input Data Connection

The PowerMonitor 500 unit with EtherNet/IP communication supports Class 1

connections to its nine assembly instances. To set up a Class 1 connection to a

selected assembly instance with a Logix controller, follow these steps.

1. Open the controller program offline in the Logix Designer application (or

online in Program mode if you are using a ControlLogix controller).

2. In the I/O configuration tree, right-click the Ethernet communication

module (for example, 1756-EN2T), and choose New Module.

3. From the Communication pull-down menu, choose ETHERNET-

MODULE Generic Ethernet Module.

Path

Method

<Ethernet Module, Port (always 2 for Ethernet), Power Monitor IP Address>

CIP