Configuration - digital outputs: read and write – Rockwell Automation 1420 PowerMonitor 500 User Manual

Page 58

Advertising
background image

58

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013

Appendix A

PowerMonitor 500 Unit Data Tables

Table 29 - Configuration - Digital Outputs: Read and Write

Modbus

Address

Length

(words)

Description / Units

Data Format

Notes

304865

1

Digital output channel 1: enabling

UINT

0=Remote
1=Alarm
2= Pulse

304866

1

Digital output channel 1: output
working mode

UINT

0=NO
1=NC (only if selected ‘Alarm’ type)

304867

1

Digital output channel 1: linked
alarm

UINT

0=AL1
1=AL2
2=AL3
3=AL4 (only if selected ‘Alarm’ type)

304868

1

Channel 1: linked counter variable

UINT

0=Total kWh+
1=Total kVARh+
2=Total kWh-
3=Total kVARh-
4=Partial kWh+
5= Partial kVARh+
6= Partial kWh-
7= Partial kVARh-

304869

2

Digital output channel 1: pulse

REAL

Pulse weight (kWh/pulse or kVARh/pulse)
Value min = 0.001
Value max = 9999.9

304871

1

Digital output channel 2: enabling

UINT

0=Remote
1=Alarm
2= Pulse

304872

1

Digital output channel 2: output
working mode

UINT

0=NO
1=NC (only if selected ‘Alarm’ type)

304873

1

Digital output channel 2: linked
alarm

UINT

0=AL1
1=AL2
2=AL3
3=AL4 (only if selected ‘Alarm’ type)

304874

1

Channel 2: linked counter variable

UINT

0=Total kWh+
1=Total kVARh+
2=Total kWh-
3=Total kVARh-
4=Partial kWh+
5= Partial kVARh+
6= Partial kWh-
7= Partial kVARh-

304875

2

Digital output channel 2: pulse

REAL

Pulse weight (kWh/pulse or kVARh/pulse)
Value min = 0.001
Value max = 9999.0