PowerMonitor 500 Unit Data Tables

Table 25 - Configuration - Alarms

Modbus

Address

Length

(words)

Description / Units

Data Format

Notes

Block address
+0

1

Alarm N - Enabling

UINT

Value=1: alarm N enabled Value=0: alarm N disabled All other
values are considered as value=0

Block address
+1

1

Alarm N - Variable type to be linked
to

UINT

Refer to the Connected Variable List (

Table 43

)

Block address
+2

1

Alarm N - Delay ON activation (s)

UINT

Value min=0 Value max=3600 If the set value exceeds the allowed
range, the instrument automatically sets the value to 0

Block address
+3

2

Alarm N – Set point 1

REAL

Value min = -9999M Value max = 9999M If the set value exceeds
the allowed range, the instrument automatically sets the value to
0.000

Block address
+5

2

Alarm N – Set point 2

REAL

Value min = -9999M Value max = 9999M If the set value exceeds
the allowed range, the instrument automatically sets the value to
0.000

Block address
+7

9

Reserved

Table 26 - Configuration - RS-485/RS-232 Communication

Modbus

Address

Length

(words)

Description / Units

Data Format

Notes

304356

1

Clock format

UINT

0=24h/12h 1=AM-PM

304357

1

Clock daylight-saving

UINT

Value=0: NO Value=1: YES

304358

1

Clock calendar: Year

(1)

UINT 2009…2099

304359

1

Clock calendar: Month

(1)

UINT

1…12

304360

1

Clock calendar: Day

(1)

UINT 1…31

304361 1

Clock:

Hour

(1)

UINT 0…23

304362

1 Clock:

Minutes

(1)

UINT

0…59

304363 1

Clock:

Seconds

(1)

UINT 0…59

304364

1

Daylight-saving: month in which to
increase the hour (+1H)

UINT 1…12

304365

1

Daylight-saving: Sunday in which to
increase the hour (+1H)

UINT

0…4 (0= last Sunday of the month)

304366

1

Daylight-saving: hour in which to
increase the hour (+1H)

UINT

0…23 (24h format only)

304367

1

Daylight-saving: month in which to
decrease the hour (-1H)

UINT 1…12

304368

1

Daylight-saving: Sunday in which to
decrease the hour (-1H)

UINT

0…4 (0= last Sunday of the month)

304369

1

Daylight-saving: hour in which to
decrease the hour (-1H)

UINT

0…23 (24h format only)

304401 1

RS-485

instrument

address

selection

(2)

UINT

Value min = 1 Value max = 247 If the set value exceeds the allowed
range, the instrument automatically sets the value to 1

304402

1

RS-485 baud rate selection

(2)

UINT

Value=0: 9600 Value=1: 19200 Value=2: 38400 Value=3: 115200
All other values are considered as value=0

304403

1

RS-485 parity selection

(2)

UINT

Value=0: No parity Value=1: Odd parity Value=2: Even parity All
other values are considered as value=0

(1) The values are updated only after sending the ‘update clock’ command.

(2) The values are updated only after sending the ‘update serial communication setting’ command or switching off and on the instrument.