Digital filtering operation, Digital filter programming examples – Rockwell Automation 1420 PowerMonitor 500 User Manual

Page 30

Advertising
background image

30

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013

Chapter 3

Unit Configuration

Digital Filtering Operation

Digital filtering smooths out the display of fluctuating values. The parameter

FILTER S defines the operating range of the filter. This operating range is

represented as a yellow band (each small square is one digit). While the measured

value (red curve in figure) is within this band, the filter is active. Once the value

exceeds the operating range, the filter is deactivated and a new band is active

around the new value. The range of fluctuation (in digits) is a good starting value

for such parameters.

The parameter FILTER CO represents the filtering coefficient. The higher the

FILTER CO, the smoother the curve of the displayed values (black in figure).

There is not a theoretical rule to define this parameter, it is set in the field. One

rule is to start with the value of the FILTER S coefficient and then increase

FILTER CO until the desired stability is reached.

The digital filter affects the values retransmitted both via serial communication

and analog output.

Figure 19 - Digital Filter

Digital Filter Programming Examples

These sections give digital filter programming examples.

Example 1

This example describes how to stabilize the displayed value of the VL-N variable,

which fluctuates between 222V and 228V. The parameters of the digital filter

have to be programmed as follows.

FILTER S: The variable fluctuates within the mean value whose amplitude is

equal to ±0.75% of the full scale rated value of the variable itself (obtained by the

following calculation: (228-222)/ 2= ±3V, then ±3*100/400V= ±0.75% where

400V is the phase-neutral rated value of a 1420-V2 unit input). The ‘range’

parameter, representing the action range of the digital filter, is to be programmed

to a value that must be slightly higher than the percentage amplitude of the

fluctuation, for example, 1.0%.

No filter action

Digital F

luc

tua

tion

Advertising